Model
APCSC3000
Net weight (Equipment only) - Kg (lb)
36 (79)
Shipping weight - Kg (lb)
47 (102)
Dimensions - H x D x W - mm (in)
 
876 x 370 x 455 
 
(34 x 15 x 18 )
Voltage/Frequency/Phase
220/240 VAC - 50 Hz - 1 Ph
Power input
1640 W
Operating current
7.7 A
Capacity - 
Total kW (BTU/hr)
2.877 (9616)
Fuse rating: 
 
Fuse 1
 
Fuse 2
 
AC 250V, F1A
 
AC 250V, T3.15A
Dehumidifying capacity - 
l/h
 (
gal/h)
1.2 (0.32)
Condensate tray capacity
1 L (1.05 quart)
Refrigerant - Kg (lb)
R-410A - 0.53 (1.17)
Refrigerant Global Warming Potential (GWP)
R-410A - 1900
Timer
24 hour
Air flow volume - 
M
3
/sec
 (
CFM
)
0.12 (244)
Operating Range - 
°C
18.3 - 35
Sound Level - dB(A)
 
with exhaust duct: High/Low
 
without exhaust duct: High/Low
 
56/55
 
56/54
MODE
InRo
om
 SC
TEMP
MODE
InRoom
 SC
TEMP
na3399a