A.O. Smith VB/VW- 750 User Manual

Page of 52
5
CAPACITY AND FLOW DATA
TABLE 3. RECOVERY CAPACITIES.
               
        
TABLE 4. PUMPING PERFORMANCE GUIDE.
 
          
             
   
 
 
 
 
 
VB MODELS - FLOW, HEAD LOSS AND TEMPERATURE RISE
 
 
20F° (11°C)  t 
30F° (17°C)  t 
40F° (22°C)  t 
Maximum Flow Rate 
Minimum Flow Rate
  MODEL 
GPM LPH  P FT  P m  GPM  LPH  P FT  P m  GPM  LPH  P FT  P m  GPM  LPH  P FT  P m  T °F  T °C  GPM  LPH  P FT  P m  T °F  T °C
 VB-500  42  159  1.8  0.5  28  106  1.3  0.4  21  79  1.0  0.3  100 379  3.8  1.2  8  4  21  79  1.0  0.3  40  22
 VB-750  63  238  2.9  0.9  42  159  2.1  0.6  32  121  1.8  0.5  110 416  4.3  1.3  12  7  32  121  1.8  0.5  40  22 
 VB-1000  85  322  3.9  1.2  56  212  2.8  0.9  42  159  2.3  0.7  120  454  4.9  1.5  14  8  42  159  2.3  0.7  40  22
Model 
No.
Input 
Rating 
Btu/hr
Output 
Rating 
Btu/hr
Water 
Flow
Temperature Rise - °F (°C)
40
60
80
90
100
120
140
(22)
(33)
(44)
(90)
(56)
(67)
(78)
VW-500
500,000
421,500
GPH
1,268
845
634
563
507
423
362
LPH
4,797
3,198
2,399
2,132
1,919
1,599
1,371
VW-700
750,000
633,750
GPH
1,901
1,268
951
845
761
634
543
LPH
7,196
4,797
3,598
3,198
2,878
2,399
2,056
VW-1000
1,000,000
845,000
GPH
2,535
1,690
1,268
1,127
1,014
845
724
LPH
9,595
6,397
4,797
4,264
3,838
3,198
2,741