INSPECTION AND SERVICE
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
8 716 113 389b (09/07) 
40
SER
V
IC
IN
G
&
 SP
A
RES
INSPECTION AND SERVICE
Re-commission the burner:
1
Align burner combustion head (A) into the
boiler housing tube with gasket (B)
correctly fitted.
Push firmly down to compress the gasket (B).
Tighten burner retainers (C) sufficiently to
ensure a good seal.
IMPORTANT:
Ensure the gasket is a good seal between
the burner combustion head and the boiler
housing to prevent flue gases escaping.
Refit flexible air duct and secure with clip (D).
2
Plug burner lead (E) into control box (F).
Connect an oil pressure gauge to the oil 
pump, run the burner and check the oil 
pressure is correct for the required boiler 
output. Check that the smoke reading is 
between 0 and 1, if the smoke reading is 
above 1 check the air setting. If the air 
setting is correct check that the burner has
been reassembled correctly. 
Allow the boiler to warm up then check the 
combustion settings are correct as         
indicated in the table below, adjust the 
CO
2
if necessary using the air shutter. 
When the combustion is correct turn off the
boiler, remove the pressure gauge and refit 
the blanking plug and plastic cover.
Refit panels:
3
Refit the top panel and press down to
compress the seal when fitting the
securing screws.
 Push the front panel up behind the top 
panel and push in at the base to secure
the screws with the tool provided.
After service handover:
Make a note of the date of any water treatment.
Set the controls back to the users
requirements.
Complete the service interval record at the
back of this manual and a CD11 or an 
equivalent form.
If the appliance is unused and exposed to
freezing conditions; shut off all the mains
supplies, isolate the boiler and drain the
system and boiler, including the secondary 
heat exchanger.
%CO
2
NOMINAL BOILER RATING AT NORMAL OPERATING 
TEMPERATURE USING 28sec KEROSENE:
NOZZLE
12/18 - Bentone Sterling 40 Burner:
OIL PUMP
PRESSURE
(p.s.i.)
FUEL
FLOW RATE
Kg/h
l/h
APPROX.
FLUE GAS
TEMP 
°C
APPROX.
AIR
SETTING
APPLIANCE
INPUT
OUTPUT
kW
Btu/hr
kW
Btu/hr
0.35 80
°SR
0.45 80
°S
0.50 80
°ES
115
115
140
1.04
1.29
1.55
1.32
1.63
1.96
66
70
73
11.5
12.0
12.5
 2.5
 4.5
5.25
42300
52900
63500
 12
 15
 18
40900
51200
61400
12.4
15.5
18.6
25/32 - Riello RDB Burner:
0.75 60
°ES
0.75 60
°ES
0.85 60
°ES
105
140
150
2.15
2.45
2.75
2.72
 3.1
3.48
78
80
83
11.5
12.0
12.5
 3.0
 4.0
 5.0
87000
99300
         111600
 25
28.5
 32
85300
97200
109200
25.5
29.1
32.7
18/25  - Bentone Sterling 50 Burner:
0.50 80
°EH
0.55 80
°EH
0.65 80
°EH
130
145
150
1.56
1.86
2.17
1.98
2.36
2.75
72
79
82
11.5
12.0
12.5
4.25
 6.0
 8.0
63500
75750
88000
 18
21.5
 25
61400
73400
85300
18.6
22.2
25.8
E
A
B
C
D
F