supply pressure and adjust to ensure a supply
pressure between 4.0 and 10.5 inches water 
col 
umn natural gas (13.0" w.c. for propane) while 
the appliance is firing at 100% of rated input.
7. 
This is a reference pressure only and is not field 
adjustable. An ap 
pli 
ance supplied with a 
minimum of 4 inch 
es water column of gas supply 
pres 
sure will operate at the correct man 
fold 
pressure as the burner input var 
ies with 
temperature demand.
8.
Close the two gas pressure test cocks on the 
pressure test tree and remove the hoses to the 
manometer.
9.
Close the front control panel.
IMPORTANT
Upon completion of any testing on the gas system, leak test
all gas connections with a soap solution while the main
burner is firing.  Immediately repair any leak found in the
gas train or related components.  DO NOT operate an
appliance with a leak in the gas train, valves or related gas
piping.
WATER CONNECTIONS
AIR INLET
GAS
WATER OUTLET
WATER INLET
FLUE OUTLET
FIG. 37   Water Connections
– – – – = FIELD CONNECTED
 
MANIFOLD GAS PRESSURE
3.5" W.C.=  gas
P
FIG. 36   Manifold Gas Pressure Measurement