NOTE:
Allow 10 seconds for data shown in the display screens to
update when viewing or making adjustments to any of the
six adjustable points.
POINTS FROM INFORMATION
VISIBLE FROM THE SCREEN OF
THE COMMAND DISPLAY
1.
Calculated Set Point — The water temperature as 
adjusted by an optional outdoor reset function 
used on a heat 
ing boiler only.  If no outdoor reset 
function is used, this displays the same 
temperature as the set point.  Outdoor Air Reset 
function not available on a water heater application.
2.
Set Point Temp — The desired water temperature 
as adjusted by the owner/operator.  This becomes
the lowest boiler operating temperature when an
optional outdoor reset function is used (Changeable Point
from the Com mand Display).
3.
Return/Inlet Temp — The tem per a ture of the water 
entering the boiler or water heater, a basic thermometer
function to display inlet water temperature.
4.
Supply/Outlet Temp —  The  tem per a ture  of  the 
water leaving the boiler or water heater, a basic 
thermometer func 
tion to display outlet water 
temperature.
5.
Temp. Rise — The difference be 
tween inlet and 
outlet water tem 
per 
ture at the boiler or water 
heater to show the water temperature rise.
6.
Status — Displays current status of the control as 
the appliance is going through its firing sequence 
and possible faults that could occur and the 
condition of each.  See Status Point Modes and 
Alarms.
7.
O.A. Lockout
— The maximum out 
door air 
temperature where the boiler will continue to 
operate.  When the outdoor temperature rises 
above this setting, no heat should be needed for 
the building and the boiler will lock 
out and not 
fire.
8.
O.A. Max — The warmest outdoor air temperature 
where the boiler reset function will begin to 
function and operate the boiler at the initial 
set point temperature. The boiler set point will 
increase based on a cor 
re 
spond 
ing drop in outdoor 
temperature below this temperature.
9.
O.A. Min — The coldest outdoor air temperature 
where the boiler reset function will reach a 
maximum boiler water temperature.  No additional 
reset (increase) in boiler temperature will occur 
past this point as outdoor tem 
per 
ture continues 
to drop lower (Change 
able Point from the 
Command Display).
10.
O.A. Temp
— A display of the outdoor air 
temperature as sensed by the optional outdoor air 
reset sensor.
11.
Max. SetPoint — The maximum water temperature 
the boiler or water heater may be set to operate at
(Changeable from the Command Display).   
12.
Min. SetPoint — The minimum water temperature the
boiler or water heater may be set to operate at. This
temperature is established in the configuration process
at the factory.
13.
Total Run Time — The accumulated number of 
hours that the boiler or water heater burner has 
been in operation.  Time is accumulated in one hour 
increments and can total up to 99,999 hours before 
rolling over to restart the accumulation process.
14.
Sequencing Type
— The type of sequencing 
selected for operation of multiple units, FOFO, 
FOLO, etc., when ordered as an option.  See 
“Sequencing Options” (Changeable Point from 
the Command Display).
15.
Percent Modulation — The percent of maximum 
input that the burner is actually firing at.  This 
may vary from 25% up to 100% of rate based on demand.
16.
Auxiliary Relay — The “ON” or “OFF” status of an 
additional relay to in 
di 
cate a specified function of 
the unit.
17.
Percent Bypass  — The percent that the bypass valve is
open to allow heat 
ed discharge water to be 
recirculated into the inlet of the primary heat  exchanger 
in order to control condensate formation on the primary 
heat exchanger.  0% indicates that the valve is fully 
closed and  100% in di cates that  the valve is fully open.  
The percentage will vary with valve operation.
18.
Bypass Temp.
— A display of the water 
temperature in the inlet to the primary heat 
exchanger after being mixed with hot discharge 
water from the bypass piping when the bypass 
valve is open.
19.
Operating Sensor — A display which indicates 
the location of the operating sensor in the unit.  
The operating sensor may be in the 
Return/Inlet or Supply/Outlet of the boiler or water
heater  (Changeable Point from the Command Display).
20.
Heater Pump — The “ON” or “OFF” sta 
tus of the 
integral circulating pump for the boiler or water 
heater.
21.
Heater I.D. —  An indication of whether the unit 
is a boiler or water heater (Changeable Point 
from the Command Display).