SEQUENCE OF OPERATION
1.
The power switch is placed in the “ON” position and 
the run/stop switch is in the “RUN” position.
2.
120 VAC Power is supplied to the con 
trol junction 
box and to the integral pump.
3. 
120 VAC Power is supplied to the con 
trol 
Transformer, Ignition Module and Excel 10.
4. 
The bypass valve will synchronize on initial 
startup only.
5.
24 VAC is supplied to all low volt age controls.
6.
Integral pump starts and is proven by a Flow 
Switch.
7.
Command Display Set Point (Operating 
Temperature) is set to call for heat.
8.
Excel 10 Controller initiates a start-up sequence 
by checking the Tem 
per 
ture Sensors and input 
signals from the safety controls.
9.
Excel 10 enables the Ignition Mod ule.
10.
Ignition Module enables the Vari 
able Frequency 
Drive.
11.
Excel 10 Controller drives the Variable Frequency 
Drive. 
12. The 
Variable Frequency Drive sup 
plies the 
Combustion Air Blower with 230 VAC 3  phase
power.
13.
Combustion Air Blower starts op er a tion and drives to 100%
speed for prepurge.
14.
Blower makes the low air switch contacts to enable the 
Ignition Module.
15.
Blower cycles down to 50% speed and the  Ignition
Module initiates the heat-up sequence of the Hot
Surface Igniter.
16.
Hot Surface Igniter proves 1800°F (982°C) 
Ignition Temperature by current draw through the  
Ignition Module.
17.
The Ignition Module supplies voltage to the 
Variable Ratio Gas Valve and the Redundant Gas 
Valve.
18.
Relay contacts prove operation of the Igniter, Gas 
Valves and Safety Switches to the Excel 10. 
19.
Variable Ratio Gas Valve senses the pressure from 
the Combustion Air Blower and supplies gas to 
the orifice and into the Blower inlet to pre-mix. 
20.
The Gas/Air mixture is forced into the Burner and 
out of the Burner Ports under pressure.
21.
Hot Surface Igniter lights the Gas/Air mixture and
then serves as a flame sensor to prove Main Burner Flame
by rectification.
22.
Burner is now in a soft start fir ing at 50% of rated input.
23.
Excel 10 Controller signals the Variable Frequency 
Drive to adjust blower speed based on desired 
water temperature Set Point.
24.
Burner input rate is variable down to 25% of rate 
or up to 100% of rate as required to satisfy the
Set Point pro 
grammed into the Command Display.
25.
Excel 10 Controller senses Inlet Water Temperature to the
Primary Heat Exchanger and provides a signal
to adjust the floating point Bypass Valve
(based on return/inlet control choice).
26.
Bypass Valve adjusts position to maintain an inlet 
temperature to the Primary Heat Exchanger above the
dew point of flue products.
27. 
Operation of the Bypass Valve main 
tains water 
temperatures above the dew point of flue products 
to ensure that condensate formation occurs only 
in the Secondary Heat Exchanger.
Heat Transfer Process
28.
Burner Input continues to increase until water 
temperature reaches the Set Point temperature.
29.
Burner Input may stabilize at a fixed rate where 
demand equals input.
30.
Burner Input will decrease rate when water 
temperature exceeds tem 
per 
ture Set Point and 
demand.
31.
Heated products of combustion pass over the 
Primary Heat Exchanger trans 
fer 
ring heat to the 
water.