Lochinvar 000 User Manual

Page of 80
72
5.
Be sure the pipes between the water heater or hot 
water supply boiler and storage tank are not less 
than 3 inch (76.2 mm) diameter for up to 70 
equivalent feet (21.2 m) of pipe to and from the 
heater.  If maximum equivalent length for the
specified pipe diameter is exceeded, larger diameter 
pipe may have to be installed to achieve correct flow 
and temperature rise.
6.
Common manifold piping for multiple unit 
installations will require larger minimum pipe sizes 
and tank circulating tappings to ensure proper flow.  
If the temperature rise is too low, the water velocity is too high.
Adjust as follows:
1.
Temperature rise can be increased by slowly 
closing the field-installed ball valve in the outlet 
piping from the water heater to the storage tank to 
achieve the proper temperature rise. 
2.
Sustained high water velocity and low temperature 
rise may result in pitting or erosion of the copper 
tubes in the heat exchangers. This is a
non-warrantable failure. Temperature rise must be 
properly adjusted to achieve the specified flow rate.
3.
Once temperature rise has been prop 
er 
ly set,  
reconnect the power leads to the bypass actuator.  
4.
Turn power on and place the run/stop switch in 
the “RUN” position and allow the bypass valve to 
go through the synchronization process before it 
begins normal operation. 
WARNING
Moving the bypass handle while appliance is firing can
result in abnormally high water temperature that may
cause sudden relief valve discharge.
CAUTION
Temperature rise cannot be adjusted when the burner is
firing at less than 100% of rate input.
WATER CHEMISTRY
NOTE:
Water temperature rise and maximum flow data are based
on heating potable water with a hardness of 5 to 25 grains
per gallon and total dissolved solids not exceeding 350 ppm.
The required temperature rise and the standard integral pump are
sized based on the heating of potable water with a hardness of 5 to
25 grains per gallon and a total dissolved solids not
ex ceed ing 350 ppm.  Consult the man u fac tur er when heating
potable water ex ceed ing these specifications.  Heating of high
hardness and/or high total dissolved solids water may require a
larger circulating pump, an optional cupro-nickel heat exchanger
and a re vised temperature rise specification based on the water
chemistry of the water to be heated. Water with a hardness of less
than 5 grains per gallon will usually have a low pH which can be
aggressive and corrosive causing non-warrantable damage to the
heater, pump and associated piping.  Corrosion due to water
chemistry generally shows up first in the hot water system be cause
heated water increases the rate of corrosive chemical reactions.