Crown Boiler 24-07 User Manual

Page of 90
11
Figure 2:  Boiler Foundation
Figure 3a:  Typical Arrangement for Stub Vent
C
.  PROVIDE AIR SUPPLY AND VENTILATION to 
accommodate proper combustion.
 
For commercial and industrial equipment, permanent 
facilities for supplying an ample amount of outside air 
shall be provided in accordance with the following.
 
For boiler rooms adjacent to outside walls, and where 
combustion air is provided by natural ventilation from 
the outside, there shall be a permanent air supply inlet 
having a total free area of not less than 1 sq. inch per 
4,000 Btu per hr. (35 sq. inch per gallon per hour) 
(5.5 cm
per kw.) of total input rating of the burner or 
burners and in no case less than 35 sq. inch (0.425m
2
).
 
For boiler rooms not adjacent to outside walls, the 
combustion air shall be supplied in a manner acceptable 
to the authority having jurisdiction.
1.  In the absence of local requirements, the confined 
space shall be provided with two permanent 
openings, one in or near the top of the room and one 
near the bottom.  The openings shall communicate 
by means of ducts, with the outdoors or to such 
spaces (crawl or attic) that communicate with the 
outdoors.
a.  Where communicating by means of vertical 
ducts, each opening shall have a free area of not 
less than 1 sq. inch per 4,000 Btuh (35 sq. inch 
per gph) (5.5 cm
2
 per kw) of total input rating of 
all appliances in the enclosure.
b.  If horizontal ducts are used, each opening shall 
have a free area of not less than 1 sq. inch 
per 2,000 Btuh (70 sq. inch per gph.) (11 cm
2
 
per kw) of total input of all appliances in the 
enclosure.
D
.  CHIMNEY  OR  VENT
 
The Series 24 boiler is designed for forced draft firing 
and may be used with a conventional natural draft 
stack (15’ minimum height) or a stub vent, sometimes 
called a diesel stack (see Figure 3a).  See Table I for 
the proper vent outlet size. For low silhouette vent 
terminations, see Figure 3b. Draft controls are not 
normally required, although they may be used on 
installations where a natural draft stack is used or on 
multiple boiler installations with a common stack.  The 
boiler is provided with a breeching damper, which 
should be adjusted to maintain a positive pressure of 
0.1” W.C. in the vent connector box during burner high 
fire operation (see breeching pressure sensing port in 
Figure 1).
WARNING
Failure to supply adequate air to the boiler
will result in unsafe boiler operation.