Jotul GF3 DVII User Manual

Page of 28
Restrictor Sliders
First Restriction
Setting - install
screw into the
OUTER hole of
sliders.
Second Restriction
Setting - screw
installed into
MIDDLE hole of
slider.
12
12
12
12
Figure 5.  Vent restrictor settings.
Horizontal Venting Requirements
Follow these guidelines if any part of the installation
incorporates a horizontal run or terminates horizontally.
• The maximum horizontal run made directly off the rear
of the stove shall be no more than 12" and must then be
connected to a 14" snorkel cap (Simpson Dura-vent #982).
• The horizontal termination cap must maintain a 3"
clearance to any overhead combustible projections
exceeding 2 1/2" or less. Maintain 12" clearance from
projections exceeding  2 1/2".  See Figure 8, page for
complete termination clearance information.
• Any horizontal run of vent must be level or have a 1/4"
rise for every foot of run toward the termination cap.
     NEVER ALLOW THE VENTING TO SLOPE DOWNWARD,
AS HIGH TEMPERATURES MAY RESULT AND CREATE A
HAZARDOUS CONDITION.
• Vent Pipe Clearance to Combustible Materials: For all
horizontal runs, a 2" top clearance and a 1" side and
bottom clearance must be maintained.
• Wall Pass-through: A minimum 10" X 10" square cutout
is required to maintain proper clearances through
combustible wall construction. The opening must be
framed in. Simpson Dura-Vent Wall Thimble #942 or
Secure Vent Wall Radiation Shield SV4RSM must be
used for the wall pass-through. Optional decorative
plates are available to finish the interior side of the
wall pass-through.
• IMPORTANT: Follow the vent manufacturer’s installa-
tion instructions provided with each vent component.
• DO NOT FILL AIR SPACE WITH ANY TYPE OF INSULATION.
• MAINTAIN THE PROPER CLEARANCES TO THE TERMI-
NATION CAP. SEE FIG. 10.
• Do not recess the termination cap into a wall or siding.
• Install a Vinyl Siding Standoff between the vent cap
and the exterior wall (Simpson Dura-Vent #950). to
protect vinyl siding from overheating.
Figure 6.  Minimum Vertical Vent - Simpson Dura-
Vent part numbers shown.
7
NOTE:
SHORT  LEGS
REDUCE THE
HEIGHT BY
2  1/4”.
24” length
#904B
90° Elbow
#990B
55 3/4”
Floor to
centerline of
minimum
vertical rise
123
123
123
123
123
123
123
Figure 7.  Horizontal terminal to corner.
Simpson Dura-Vent 45°
Elbow #945B
12” Max.
Horizontal run
into a 14”
Snorkel
Simpson Dura-
Vent (#906B)
14” Snorkel
Simpson
Dura-Vent
(#982)
12” Max. Horizontal
run into a 14” Snorkel
Simpson Dura-Vent
(#906B)
Figure 7a.  Horizontal terminal directly off  stove
must use a 14” Snorkel termination.
Rear Exit
Centerline
24 3/4”
628 mm
Wall Thimble
#942B
Horizontal Length
12” Max.
Wall Plate
#940B