Drolet 58991 User Manual

Page of 27
 
12
REDUCED CLEARANCES 
You may decrease the clearances by installing heat radiation shields between the walls or 
the ceiling and the stove.  These heat radiation shields must be installed permanently, and 
can include sheet metal, a rigid non-combustible sheet or a masonry wall. 
 
Clearances of not less than 1" (25 mm) and not more than 3" (76 mm) between the bottom 
of the shield and the floor and not less than 3" (76 mm) between the top of the shield and 
the ceiling must be respected to allow vertical air circulation behind the shield. 
 
The shield must extend 20" (500 mm) above the stove top and 18" (450mm) to each side 
of the stove. 
 
Following the installation of such a heat radiation shield, the clearances mentioned on the 
stove certification plate may be reduced as stated in the following table. 
 
 
TYPE OF PROTECTION 
Reducing Clearances With 
Shielding 
Sides and 
Rear/Back 
Top 
Sheet metal, a minimum of 0,013" (0,33 mm) spaced 
out at least 7/8" (21 mm) by non-combustible spacers.
67% 50% 
Ceramic tiles, or an equivalent non-combustible 
material on fire-proof supports spaced out at least 7/8" 
(21 mm) by non-combustible spacers. 
50% 33% 
Ceramic tiles, or an equivalent non-combustible 
material on fire-proof supports with a minimum of 
0,013" (0,33 mm) sheet metal backing spaced out at 
least 7/8" (21 mm) by non-combustible spacers. 
67% 50% 
Brick spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
50% N/A 
Brick with a minimum of 0,013" (0,33 mm) sheet metal 
backing spaced out at least 7/8" (21 mm) by non-
combustible spacers. 
 
67% N/A 
Source: CSA Standard B365-1991, Table 4, Page 27