Enviro C-10985 User Manual

Page of 31
� ��
���� ���
���� ��� ������� ��� ��
�� ����� ��� ����� ���
���� �� ��� ������ ������
���� ��������
���� ������
���� ���� ����
������� ������
������� �����
�������� ���� ����
����� ��� ��� ����
���� �������
����� ��� ���� �������� ����
�������� � ������ ���� ���
���������� �� �������������
Figure 15: Inside Vertical Installation. 
1.  Choose a stove location that is ideal.  See the 
section “D
ECIDING
 W
HERE
 
TO
 L
OCATE
 
YOUR
 P
ELLET
 
A
PPLIANCE
.” 
2.  Place  a  non-combustible  hearth  pad  where 
necessary.
3.  Place the unit on the hearth pad (if installed 
on  a  combustible  surface)  and  space  the 
unit in a manner so when the pellet vent is 
installed vertically, it will be 3” (7.5 cm) away 
from a combustible wall.
4.  Install the tee with clean out.
5. 
I
nstall  the  pellet  vent  upward  from  there.  
When  you  reach  the  ceiling,  make  sure 
that  the  vent  goes  through  the  ceiling  fire 
stop.    Maintain  a  3”  (7.5  cm)  distance  to 
combustibles and keep attic insulation away 
from  the  vent  pipe.  Maintain  an  effective 
vapor barrier.
6.  Finally, extend the pellet vent to go through 
the roof flashing.
7.  Ensure that the rain cap is approximately 24” 
(600 mm) above the roof.
To  accomplish  a  outside  vertical  pipe  installation, 
follow  steps  1  through  5  in  the  “I
NSIDE
  V
ERTICAL
 
I
NSTALLATIONS
 - F
REESTANDING
” section and then finish it 
by performing the following (refer to Figure 16).
1.  Install a tee with clean out on the outside of the 
house.
2. Install PL vent upward from the tee. Make sure 
that you install support brackets to keep the vent 
straight and secure.
3. Install ceiling thimble and secure the flashing as 
you go through the roof.
4.  Ensure  that  the  rain  cap  is  approximately  24” 
(600 mm) above the roof.
13
Installation
I
NSIDE
 V
ERTICAL
 I
NSTALLATIONS
:
Figure 16: Outside Vertical Installation. 
O
UTSIDE
 V
ERTICAL
 I
NSTALLATIONS
:
Rain cap
Flashing
24"
(61 cm)
4"
(10 cm)
Tee with
cleanout
3" (7.5 cm)
Clearance
Support
bracket
Type "PL"
vent