Enviro 1200 Freestanding User Manual

Page of 45
Floor Protection
Combustible Floor
Masonry Fireplace
Rain Cap
Steel Plate or Flashing
Rigid Stainless
Steel Liner
Damper Removed
or Fastened Open
Clean-out tee
Chimney
Support and Clamp
Clean-out
cover
Flexible Stainless
Steel Section
Stainless Steel
Connector Pipe
Listed Liner
Stove pipe must
end higher than liner
Figure 27: Freestanding Installation into existing fireplace.
installer.
Many venting manufacturers 
have  listed  kits  available  to 
connect a stove to a masonry 
fireplace.  Always  follow 
the  vent  manufacturer’s 
installation instructions. 
The existing damper 
may have to be removed 
to allow installation.
Installation
M
ASONRY
 F
IREPLACE
 I
NSTALLATION
 - F
REESTANDING
:
Unless you are experienced, we recommend installation by your dealer or a professional 
M
OBILE
 H
OME
 I
NSTALLATION
 - F
REESTANDING
:
SPECIAL  REQUIREMENTS:  Pedestal  models  1200  and  1700  are  approved  for  mobile  homes.  All 
freestanding installation requirements in “
Installation Of A Listed, Factory Built Chimney”, must comply 
with all local codes that may apply, and the following must be met:
VENTING:
In Canada:
 Any ULC-S629 listed chimney system with the accompanying double-wall vent connector. 
In U.S.A.  Any  UL-103-HT  listed  chimney  system  with  the  accompanying double-wall  vent  connector. 
Do not connect a listed chimney of one manufacture with a listed double wall connector from another 
manufacture. 
26