Lightolier 6706S2UEM Leaflet

Page of 1
10
9
6
4
1
5
2
3
8
7
8 1/4" DIA.
9 7/8" DIA.
13 15/16" DIA.
18" DIA.
4"
1 5/16"
Specification Decorative Discus
6706S2UEM
Page 1 of 1
Ceiling or “ADA” Wall Mounted Compact Fluorescent 1 Lt. 22W
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier 
a Genlyte Thomas Company
www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2002 Genlyte Thomas Group LLC (Lightolier Division) • A0902
Features
1. Diffuser: Acrylic, injection molded and bonded into one piece assembly;
0.12" minimum thickness; 70% light transmission. Lights evenly without dis-
cernible hot spots. Integral tabs provide “twist-lock” installation; no loose
hardware, no tools required.
2. Housing: Polycarbonate, injection molded. Shatter resistant. Integral bosses
retain diffuser without loose hardware.
3. Ballast: Electronic; High power factor; Class P. See Electrical/Ballast.
4. Lamp: 22W, T5, Circline; 2GX13 base (by others).
5. Lamp Socket: Polycarbonate, 4-Pin, 2GX13 base.
6. Lamp Support Clip: .020” thick, spring steel.
7. Battery Pack: Provides 90-minute emergency lighting when AC power fails.
Long life nickel cadmium battery; charges from 120 and 277V AC. Meets
National Electric and Life Safety Code.
8. Charge Indicator Light: LED
9. Test Switch: Single pole.
10. Trim Ring: 16 gauge die formed aluminum. Brushed aluminum finish.
Mounting
Ceiling or wall (ADA compliant). Mounts to standard 4” outlet box.
Options
+ Shatter resistant polycarbonate diffuser. Add TP to end of catalog number.
+ Designates made to order only. Consult factory for lead times.
Ordering Information
Cat. No.
Finish
Wattage
Voltage
Lamping
6706S2UEM
Matte Silver
22W
120V-277V
Philips
Osram/Sylvania
FC9T5/*
FPC22/*
*Designates manufacturer’s color temperature.
Electrical/Ballast
22W Lamp
120v
277V
Total Input Watts:
25
25
Max. Line Current:
.22
.10
Power Factor:
>.98
>.98
Ballast Factor:
1.00
1.00
THD:
<10%
<10%
Starting Temp:
0°F
0°F
Emergency/Ballast
Recharge Time
Charging Current
Lumens
24 Hours
280mA
600
Labels
UL Listed, Suitable for Dry Locations.