Schneider Electric iEM3100 User Manual
76
DOCA0005EN-04
Communications via M-Bus
iEM3100 / iEM3200 / iEM3300 series user manual
Related topics
•
See the M-Bus organization website at www.m-bus.com for more information on the M-bus
protocol.
protocol.
•
•
M-Bus protocol support
The meter supports the M-Bus protocol as follows:
•
Mode 1 communications (least significant bit first).
•
Telegram formats:
— Single character
— Short frame
— Long frame
— Short frame
— Long frame
•
Function codes (C-field bits 3-0):
— SND_NKE: Initiates of communications between the master and slave.
— SND_UD: The master sends user data to the slave.
— REQ_UD2: The master requests Class 2 user data from the slave.
— RSP_UD: The slave sends requested data to the master.
— SND_UD: The master sends user data to the slave.
— REQ_UD2: The master requests Class 2 user data from the slave.
— RSP_UD: The slave sends requested data to the master.
•
Secondary addressing in accordance with the M-Bus standard.
•
Broadcast telegrams.
Related topics
•
See the M-Bus organization website at www.m-bus.com for more information on the M-Bus
protocol, including secondary addressing procedures.
protocol, including secondary addressing procedures.
•
See “Fixed data header” on page 77 for the meter-specific information required for secondary
addressing (for example, identification number, manufacturer and medium).
addressing (for example, identification number, manufacturer and medium).
M-Bus protocol implementation
M-Bus tool for viewing data and configuring the meter
The M-Bus tool provides a graphical user interface where you can view meter data and configure
meter settings. To obtain the tool, go to www.schneider-electric.com and search for your meter model
then select Downloads or contact your local Schneider Electric representative.
meter settings. To obtain the tool, go to www.schneider-electric.com and search for your meter model
then select Downloads or contact your local Schneider Electric representative.
Communications LED indicator for M-Bus meters
The communications LED indicates the status of the communications between the meter and the
network as follows:
network as follows:
Related topics
•
•
See “M-Bus tool for data display and meter configuration” on page 85 for information on obtaining
and using the M-Bus tool.
and using the M-Bus tool.
LED state
Description
The LED is flashing
Communication with the meter has been established.
NOTE: The LED flashes even if there is a communications error.
NOTE: The LED flashes even if there is a communications error.
The LED is off
There is no active communication.