Schneider Electric iEM3100 User Manual

Page of 112
90
DOCA0005EN-04
Communications via BACnet
iEM3100 / iEM3200 / iEM3300 series user manual
The following standard object types are supported:
Related topics
BACnet communications implementation
Configuring basic communication parameters
Before communicating with the meter via BACnet protocol, use the front panel to configure the 
following settings:
BACNet Interoperability Building Blocks (Annex K)
DS-RP-B (Data Sharing - Read Property - B)
DS-RPM-B (Data Sharing - Read Property Multiple - B)
DS-WP-B (Data Sharing - Write Property - B)
DS-COV-B (Data Sharing - COV - B)
DM-DDB-B (Device Management - Dynamic Device Binding - B)
DM-DOB-B (Device Management - Dynamic Object Binding - B)
DM-DCC-B (Device Management - Device Communication Control - B)
Data link layer options
MS/TP master (clause 9)
Baud rates 9600, 19200, 38400, 57600, 76800
Character set
ANSI X3.4
Supported services
subscribeCOV
readProperty
readPropertyMultiple
writeProperty
deviceCommunicationControl
who-HAS
who-Is
I-Am
I-Have
Confirmed COV notification
Unconfirmed COV notification
Segmentation
The meter does not support segmentation
Static device address binding
The meter does not support static device address binding
Networking options
None
Object type
Optional properties supported Writable properties supported Proprietary properties
Device Object
Max_Master
Max_Info_Frames
Description
Location
Local_Date
Local_Time
Active_COV_Subscriptions
Profile Name
Object_Name
Max_Master
Max_Info_Frames
Description
Location
APDU_Timeout
Number_Of_APDU_Retries
ID_800
ID_801
ID_802
Analog Input Object
COV_Increment
COV_Increment
Analog Value Object
Present_Value
Binary Input Object
BACnet component
Description
Setting
Possible values
Baud rate
9600
19200
38400
57600
76800
Mac Address
1 - 127
Device ID
0 - 4194303