Bosch D1256RB User Manual

Page of 14
D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0 
D1256RB Programming Requirements 
 
 
12 
Bosch Security Systems, Inc. | 8/06 | F01U011791B 
 
4.4.5 
Keypad (Command Center) Functions 
The following keypad function must be enabled or 
passcode required to enable the [DETECTOR RESET] 
key.  
 
#27 Reset Sensors 
Include the following items in the menu: 
 
#9 View Event Memory 
 
#10 View Point Status 
 
#12 Fire Test 
 
#21 View Log 
 
#29 Remote Program 
 
#32 Display Rev 
Refer to Figure 18
 
 
 
For the D9412GV2 Control Panel, program 
each of the keypad functions with E 
(enabled) and not P (passcode required). If 
restricting any of the keypad functions with 
a passcode is required, those functions 
must be executed from a custom function 
that includes an authorized passcode. 
Example (Refer to Figure 18.): If the 
keypad function View Memory is 
programmed as P (passcode required), and 
the passcode 125600 has authority to 
execute it, the keystrokes would be: 
[A] [4] [0] [1] [2] [5] [6] [0] [0] [E]  
 
 
 
When creating a Menu Function List for a 
keypad address, consider that the 
D1256RB Keypad does not have numeric 
keys. Ensure that: 
 
no passcode-protected keypad functions 
are in a Menu Function List enabled at 
an address that coincides with the 
installed address for a D1256RB 
Keypad. 
 
the 
CC# Menu Key Lock
prompt is set 
to 
No for the D1256RB address. 
 
Figure 18:  Example – Keypad Functions 
 
 
Keypad Functions 
#
Functions 
Command 
E/P
*
 
1 Disarm 
 
P
Master Arm Delay ? 
CMD 1 
P
Master Arm Instant ? 
CMD 11 
 
Perimeter Instant ? 
CMD 2 
P
Perimeter Delay ? 
CMD 3 
P
Watch Mode ? 
CMD 6 
Perimeter Part ? 
CMD 8 
P
View Area Status ? 
 
P
View Memory ? 
CMD 40 
10 
View Pt Status ? 
 
11 
Walk Test ? 
CMD 44 
12 
Fire Test ? 
CMD 58 
P
13 
Send Report ? 
CMD 41/42 
P
14 
Door Control ? 
CMD 46 
P
 
Cycle Door ? 
 
 
Unlock Door ? 
 
 
Secure Door ? 
 
37 
Access Control Level? 
 
P
15 
Change Display ? 
CMD 49 
16 
Change Time/Date ? 
CMD 45 
17 
Change Passcode ? 
CMD 55 
P
18 
Add User ? 
CMD 56 
P
19 
Del User ? 
CMD 53 
P
20 
Extend Close ? 
CMD 51 
P
21 
View Log ? 
 
22 
Print Log ? 
 
P
23 
User Command 7 ? 
CMD 7 
P
24 
User Command 9 ? 
CMD 9 
P
25 
Bypass a Point ? 
CMD 0 
P
26 
Unbypass a Point ? 
CMD 00 
P
27 
Reset Sensors ? 
CMD 47 
28 
Change Relays ? 
CMD 54 
P
29 
Remote Program ? 
CMD 43 
P
30 
Move To Area ? 
CMD 50 
P
32 
Display Rev ? 
CMD 59 
33 
Service Walk ? 
 
P
34 
Default Text ? 
CMD 57 
P
35 
Change Skeds ? 
CMD 52 
P
36 
Invisible Walk ? 
 
P
* 
Keypad Function options: P = Passcode;  
E = Enabled (no passcode required); 
Blank = Disabled