Bosch D9124 User Manual

Page of 4
2 | D9124 Addressable Fire Alarm Control Panel (FACP)
Event Log Storage, Viewing, and Printing
The D9124's memory log stores time, date, point, and user
ID for up to 1000 events. Programming options allow
restricting specific event reports to the central station
receiver. A programming option allows the log to record
certain functions entered at command centers.
Display the 1000 events in memory at the fire system
controller(s) or retrieve them with a single phone call by a
central station using Bosch RPS version 3.7.025 or higher.
The D9131A Parallel Printer Interface Module allows an on-
site parallel printer to print events as they are stored in the
log: recording time, date, account number, event, point ID,
point text, and if the message was transmitted to a receiver.
Inputs
The D9124 Control Panel is a 127-point addressable system
that is expandable to 246 addressable points. The control
panel receives information from alarm initiating points
through integrated devices over a two-wire multiplex zone
expansion system. Each addressable point accommodates
both normally-open and normally-closed devices with end-
of-line (EOL) resistor supervision. Each point is
programmable for fire, fire supervisory, intrusion, or access
control applications.
Outputs
System notification appliance capacity can be extended
beyond the two supervised circuits by adding D8129 Octo-
relay Modules. Up to 128 relay outputs can be operated
through the controller or the central station, or they can be
programmed for automatic operations.
Notification appliances can be programmed for steady,
pulsed, California March Time, or Temporal Code 3
patterns. Temporal Code 3 patterns can be synchronized
using the appropriate synchronization modules.
Notification Appliance Circuits (NACs)
The D9124 FACP has two supervised, on-board NACs with
individual circuit silencing.
User Interface
A D1256 Fire Alarm keypad is visible and accessible behind
a locked, clear sliding panel located on the enclosure door.
It displays programmable text identifying specific initiating
and supervisory devices. It also provides point
annunciation, signal silence, trouble silence, detector reset,
and annunciator reset. The sliding panel lock is keyed to
match the Bosch manual pull stations for resetting the
system.
Also available as options are:
D1255R Security/Fire Keypad
D1257 Remote Fire Alarm Annunciator
D1260 Keypad
Certifications and Approvals
Region
Certification
USA
UL
AMCX: Central Station Alarm Units
(UL1610, UL1635), APAW: Police Station
Alarm Units (UL365, UL464), UOJZ:
Control Units, System (UL864)
FM
CSFM
7165-1615: 113 and 7170-1615:
144   July 2008
NYC-MEA
12-92-E, Vol. IV   12-92-E, Vol. IV
12-92-E, Vol. X11   12-92-E, Vol. 12
Hong Kong
HKFSD
Installation/Configuration Notes
Compatible Products
The following products are compatible with the D9124
FACP:
Category
Product ID
Product Description
Batteries and
Power Supply
Products
BATB-40
Battery box
BATB-80
Battery box
D126
12 V, 7 Ah standby battery
D1218
12 V, 18 Ah standby battery
D7038
Power supply address circuit module
Detectors
D285
Photoelectric smoke head
D285TH
Photoelectric smoke head with heat
D298M
Zonex smoke master base
D298S
Zonex smoke single base
FMM-462
Manual station
D603
Rate-of-rise heat detector head
D604
Fixed (135°F) heat detector head
D605
Fixed (190°F) heat detector head
Keypads and
Annunciators
D720B/R
Security and fire keypads
D1255B/R
Security and fire keypads
D1256
Fire command center
D1257
Remote fire alarm annunciator
D1260
ATM keypad
Modules
D125B
Powered loop interface module
(Dual, Class B)
D129
Initiation circuit module
(Dual, Class A)
D130
Relay module
D136
Plug-in relay
D192C
Bell supervision module
D192E
Bell supervision module