Bosch FMM-7045-D User Manual

Page of 4
FMM-7045, FMM-7045-D | Installation Instructions | 1.0  Description 
 
Bosch Security Systems, Inc. | 8/06 | F01U001402C 
 
1.0 Description 
These instructions cover the installation of Bosch 
FMM-7045 (Single Action)/FMM-7045-D (Dual 
Action) Multiplex (single-action) Multiplex Addressable 
Pull Station in a fire system supervised by a Bosch 
D7024 Series or DS9400 Series Fire Alarm Control 
Panel (FACP) with firmware revision 2.0 or greater and 
a D7039 or DS9431 Multiplex Expansion Module. 
Install, test and maintain the FMM-7045/FMM-7045-D 
according to these instructions, NFPA 72, Local Codes 
and the Authority Having Jurisdiction (AHJ). Failure to 
follow these instructions may result in failure of the 
device to operate properly. Bosch is not responsible for 
improperly installed, tested or maintained devices. 
 
These instructions contain procedures to 
follow in order to avoid personal injury and 
damage to equipment. 
 
 
 
NFPA 72 requires a complete system-wide 
functional test be performed following any 
modifications, repair, upgrades or 
adjustments made to the system’s 
components, hardware, wiring, 
programming and software/firmware. 
The FMM-7045/FMM-7045-D Multiplex Addressable 
Manual Pull Station is a UL Listed fire alarm initiating 
device. It can be connected along with other Multiplex 
devices on the D7039/DS9431 Multiplex Expansion 
Module.  
The D7024/DS9400 Series FACP supervises the entire 
multiplex loop, including the FMM-7045/FMM-7045-
D, for troubles, alarms and ground fault conditions. 
Since the FMM-7045/FMM-7045-D occupies only one 
address on the multiplex bus, the module can be 
addressed for any point within the 9 to 255 range 
allowed by the D7039/DS9431 Multiplex Expansion 
Module. 
The FMM-7045/FMM-7045-D is generally installed 
near building exits such as stairways and doors, 
allowing persons evacuating the building to activate the 
fire alarm. It is equipped with glass break rods and a 
pull handle that locks in the activated position, to allow 
easy identification of alarm activation point.  
2.0 Installation 
2.1 Operation 
The FMM-7045/FMM-7045-D (single-action) Multiplex 
Addressable Manual Pull Station is a UL Listed fire 
alarm initiating device with a multiplex input module 
connected to each pull station. 
Rotary switches are provided for convenient address 
setting. These switches eliminate the need for an 
external programmer.  
The FMM-7045/FMM-7045-D is a single-action device 
with a white pull-down lever in its center. The lever is 
easily accessible to persons standing or in wheelchairs. 
Pulling down on the lever breaks the glass rod. The 
lever then latches in the down position and activates 
the multiplex point, which then trips the fire alarm 
control panel (FACP).  
The lever cannot be reset until the proper key is 
inserted in the lock. This feature allows emergency 
personnel to determine the source of the alarm. 
2.2 
Setting the address 
The FMM-7045/FMM-7045-D’s address is set by 
positioning three rotary switches located on the front 
side of the device. The switches click when turned. The 
valid address range is 9 to 255. Check with the control 
panel’s operation and installation manual for additional 
address limitations. 
Use a flat-bladed screwdriver to position each switch 
when setting the FMM-7045/FMM-7045-D’s address. 
See Figure 1 for details. 
 
Figure 1: 
Setting the Address 
0
1
2
X X X
0
5
1
2
3
4
6
7
8
9
0
5
1
2
3
4
6
7
8
9
1
4
5
2
0
1
2
3
 
1 -  Hundreds 
2 -  Use these addresses if using the D7024 Series 
FACP with the D7039 Module. 
3 -  Use these addresses if using the DS9400 
Series FACP with the DS9431 Module. 
4 -  Tens 
5 -  Ones 
Example:  
   Hundreds      Tens       Ones     =     Address 095 
         0              9             5