DS9400 Series | Release Notes for Firmware V2.07 | 9.0 
Known Issues with Firmware Version 2.07 
 
Bosch Security Systems | 8/06 | 36925V 
 
 
Temporarily swap lines 1 and 2 on the 
control panel and see if the problem 
indication moves to the control panel’s other 
phone line channel, in which case the phone 
line is causing the problem rather than the 
line monitor. 
5.
 
Confirm that the fault message is “phone fault” 
and not “Comm fault”. 
 
“Comm fault” is often caused by failing to 
program a phone number or account 
number for phone number 2, while routing 
reports to “line 1, backup line 2”. 
 
If only one phone number is available for 
reporting, set report steering for all events to 
“phone 1 only”. 
 
“Comm fault” may also be caused if one of 
the phone lines has Telco battery voltage, 
but will not complete a call. Make test calls 
to the receiver(s) on both phone lines, 
listening for the receiver ACK tone 
6.
 
Make sure that two phone lines are available. 
 
In accordance with NFPA requirements, the 
auto-test report is sent on a different phone 
line each time it is sent. If only one phone 
line is connected to the control panel, a 
“Comm fault” will be generated on every 
other test call.