Bosch FPD-7024 User Manual

Page of 122
Appendix C: Reporting Summary for Fire Communicator
i
Notice!
For information about the receiver output when the Modem IIIa
2
 reporting format is used with
 
i
Notice!
Cause of Hazard
When the Modem IIIa
2
, SIA or Contact ID reporting formats are used, an additional numeric
identifier is sent with system trouble messages that provide a specific indication of the partic-
ular fault. This identifier is also recorded in the history log (see History log, 108).
For report codes (Items in boldface type are not programmable), see the following table:
 
Report
 
Index
Default Values
Alternate Default
 
3/1
 
BFSK
 
SIA
 
Contact ID
4/2
digit 1
4/2
digit 2
4/2
digit 1
4/2
digit 2
POINT FIRE ALARM
0
0
p
0
p
0
z0
FAz
1 110 00 zzz
POINT WATERFLOW
ALARM
1
0
p
0
p
0
z0
SAz
1 113 00 zzz
POINT SUPERVISORY
ALARM
2
0
p
0
p
0
z0
SSz
1 200 00 zzz
POINT MONITOR
ALARM
3
0
p
0
p
0
z0
UAz
1 140 00 zzz
POINT FIRE TROUBLE
4
6
p
6
p
6
Fz
FTz
1 373 00 zzz
POINT WATERFLOW
TROUBLE
5
see #4
p
see #4
p
see #4
Fz
STz
1 373 00 zzz
POINT SUPERVISORY
TROUBLE
6
see #4
p
see #4
p
see #4
Fz
STz
1 373 00 zzz
POINT MONITOR
TROUBLE
7
see #4
p
see #4
p
see #4
Fz
UTz
1 373 00 zzz
POINT FIRE DIRTY
8
see #4
p
see #4
p
see #4
Fz
FSz
1 385 00 zzz
POINT WATERFLOW
DIRTY
9
see #4
p
see #4
p
see #4
Fz
FSz
1 385 00 zzz
POINT SUPERVISORY
DIRTY
10
see #4
p
see #4
p
see #4
Fz
FSz
1 385 00 zzz
POINT MONITOR
DIRTY
11
see #4
p
see #4
p
see #4
Fz
UTz
1 373 00 zzz
POINT FIRE DISABLE
12
B
p
5
p
B
Fz
FBz
1 571 00 zzz
POINT WATERFLOW
DISABLE
13
see #12 p
see #12 p
see #12 Fz
FBz
1 571 00 zzz
10.3
 
 
102 en | Appendices
Fire Alarm Control Panels
2012.08 | 04 | F01U008458
Installation and Operation Manual
Bosch Security System, Inc.