Bosch FPD-7024 User Manual

Page of 122
4/2 POINT REPORTS
POINT 6 D2:
6
POINT 7 D2:
7
POINT 8 D2:
8
POINT 9 D2:
9
POINT 10 D2:
0
 
4/2 RPT CODS
SYSTM IN TST:
33
SYS TEST RST:
37
SILENCE:
9F
FIRE DRILL:
33
FIRE DRL RST:
37
OPEN RST RPT:
9F
LOW BATTERY:
69
LOW BATT RST:
79
AC FAILURE:
60
AC FAIL RST:
70
TEST REPORT:
30
OFF NORM TST:
33
PHONE 1 TRBL:
31
PN 1 TRB RST:
35
PHONE 2 TRBL
32
PN 2 TRB RST:
36
SYSTEM TROUB:
33
SYS TRB RST:
37
Multiplex
MUX BUS TYPE:
2 CLASS B
Appendix E: Phone Monitor Troubleshooting
 
COMM FLT/DATA LOST
A common cause of this fault condition is failing to program Phone/IP Number 2 or Account
Number 2 while some reports are directed to Phone/IP 2 Backup reports are still made to
Phone/IP Number 1. This message warns the installer that Phone/IP Number 2 is not available
if it is needed.
10.5
10.5.1
118 en | Appendices
Fire Alarm Control Panels
2012.08 | 04 | F01U008458
Installation and Operation Manual
Bosch Security System, Inc.