Bosch FPD-7024 User Manual

Page of 122
Figure 2.2: Supplemental Reporting
1 Jumper from R1 to R2
3 House phone
2 Jumper from T1 to T2
4 TELCO line
Users
The system allows up to 16 individual users, or up to 100 users when the D7039 is installed. A
personal identification number (PIN, the four-digit code entered at the keypads) and an
authority level to determine which functions can be performed can be assigned to each user.
For PINs, see Personal identification numbers (PINs), 47.
Lightning protection
i
Notice!
This system is intended for installation entirely within one building.
Metal-oxide varistors (MOVs) and spark gaps provide protection from lightning surges and
static discharges.
Battery backup calculation
To calculate the standby battery capacity required by NFPA when using the FPD‑7024, see the
two following tables:
Device
Quantity Standby
existing/device
Total
standby
Alarm existing/
device
Total alarm
FPD‑7024
Control Panel
1
200 mA
200 mA
380 mA
380 mA
FPC‑7034
Four‑Point
Expander
 
44 mA
 
156 mA
 
D7035/B Octal
Relay
1
 
8 mA + 30 mA 
2
 
8 mA + 30 mA 
2
 
D7048/B Octal
Driver Module
 
10 mA
 
10 mA
 
 
2.2.8
2.2.9
 
2.2.10
Fire Alarm Control Panels
Overview | en
13
Bosch Security System, Inc.
Installation and Operation Manual
2012.08 | 04 | F01U008458