Installation
Installation guide for UL Listed systems
FPD‑7024 UL Listings
The FPD‑7024 is UL Listed for the following:
Commercial Fire Alarm (UL Standard UL864)
Type Service: Auxiliary, Local, Central Station, and Remote Station
Type Initiating: Automatic, Manual, Sprinkler Supervisory, and Waterflow
Install the control panel according to NFPA 72 for Commercial Fire installations.
Installation considerations
Failure to install and program the control panel according to the requirements in this section
voids the listing mark of Underwriters Laboratories.
The standby battery capacity is 40 Ah at 24 VDC.
The total nominal existing must not exceed 1.25 A in standby or 4 A when in alarm.
The control panel must be mounted indoors and within the protected area.
Grounding must be according to article 250 of the NEC (NFPA 70).
Points must be connected to UL Listed, compatible devices.
The ground wire provided with the enclosure must be connected between the door and
the enclosure using the supplied nuts.
Do not program the ground start feature.
Select Phone Monitoring if the digital alarm communicator transmitter (DACT) feature is
used.
UL requirements
i
Notice!
The system must be tested after installation and after any re-programming, including pro-
gramming performed by downloading.
When used in UL Listed installations, the control panel must conform to certain programming
requirements. For a list of the required program entries specific UL Listed installations, see
the Programming features for UL864 table, 49.
Commercial Fire Alarm (Central Station [DACT] and Local)
Required Accessories
At least one Bosch Security Systems, Inc. Model F220‑P Smoke Detector with an F220
Family Base; or another UL Listed compatible smoke detector.
At least one Horn Strobe or Bell (provides 85 dB for UL985 and NFPA 72 requirements;
other UL Listed compatible devices listed for regulated 24 V can be used) is required for
this application and must be installed inside the protected area.
Four-wire detectors must be used with UL Listed power supervision devices. A
compatible UL Listed four-wire detector is the Bosch Security Systems, Inc. F220‑P in an
F220‑B6 Family Base. A compatible UL Listed relay is the Bosch Security Systems, Inc.
D275.
All points must be used with the resistor provided.
Report Programming
Program non-supervisory and supervisory reports for those points used.
Program trouble reports.
Set AC Failure Report Delay for a delay of 1 hour to 3 hours.
Set automatic test report frequency to occur at least every 24 hours.