Testing
Select any of seven special test modes using the [Test] key on the built‑in and FMR‑7033
keypads.
Walk test
The Walk Test allows a technician to alarm each point manually to ensure that detectors
connected to a point send an Alarm report to the control panel. While in this mode, the LCD
shows the system test status and the trouble sounder sounds every 10 sec. NAC outputs
activate during this test as points are alarmed and restored based on the following settings:
SHORT ACTIVE:1 second activation
LONG ACTIVE:5 second activation
NO ACTIVE:outputs do not activate
As each point is alarmed, the outputs activate once (if selected) and power is reset. As each
point is activated, alarms and restorals are logged in the control panel’s history log. When the
point returns to standby, the outputs activate twice. The control panel attempts to reset
points ten times to restore them. Points remaining alarmed when exiting from the walk test
mode cause an immediate alarm.
Communicator test
The communicator sends a test report. While communication is in progress, the Power LED
flashes. When the communication succeeds, a long keypad beep sounds, the Power LED
returns to normal, and the display returns to normal.
 