Zone
Condition
61
General Waterflow (Non-silenceable). Active when any waterflow alarm is present.
62
General Trouble. Active while any system trouble is present, not active in test and
programming modes.
63
General Alarm, Waterflow (non-silenceable). Active while any alarm, including
supervisory, is present. Remains active even while system is silenced.
Table 6.3: Pre-assigned zones
Personal Identification Numbers (PINs)
The personal identification number (PIN) is the four digit code users enter at the keypad to
gain access to the system. A PIN can be assigned to each User Number. The User Number
identifies each person using the system. There are 16 possible User Numbers (00 to 15). User
codes 00 to 99 are available with the installation of a D7039 Multiple Expansion Module. The
Authority Level assigned to each User Number determines which functions each user can
perform.
Your system can have up to 100 different PINs, each four digits long. There is one PIN for each
User Number. Attempting to assign the same PIN to multiple User Numbers results in the
three-beep error tone, and the change is not made.
User Number 00 is designated as a Programmer’s Code. It can be used to silence alarms,
reset, disable, and program the unit.
User Number 00 is shipped from the factory with the sequence of 9876. Change this code to
one of your personal preference. It is automatically assigned the highest authority. Never
program PINs with common sequences such as 1111, 1234, or 2468 because they are easily
violated.
Authority levels are assigned to PINs to determine which functions each user can perform.
For a description of the four authority levels, see the following table:
PIN authority level Allowed operations
Maximum (1)
All control panel operations, including programming, and disable
Medium (2)
System test modes, fire drill, reset, silence, view history
Minimum (3)
Silence, view history
None (0)
None
Table 6.4: PIN authority levels
Communicator Operation
The FPD-7024 contains an integrated communicator that can be optionally enabled to send
reports to a monitoring station. When enabled, operation of the communicator is fully
automatic.
i
Notice!
You must enable and configure the communicator before it works. The communicator and
phone line monitors are disabled in the default factory configuration.
 