Bosch FPD-7024 User Manual

Page of 122
Program feature or
option
Permitted in UL864
(Yes/No)
Possible settings
Settings permitted in
UL864
NAC Config
Yes
Steady
Pulsing
California March
Temporal
Wheelock
Gentex
System Sensor
Steady
Pulsing
California March
Temporal
Wheelock
System Sensor
Alarm/Trouble Open
Status
Yes
1) Alarm
2) Trouble
2) Trouble
Latching
Yes
1) Yes
2) No
1) Yes for Alarms
Heartbeat Interval
Yes
001 - 255
001 - 090
Ring Count
Yes
00 - 15
00
PIN Required on
Remote Keypad
Yes
0) No
1) Yes
1) Yes
NAC Silence Mode
Yes
1) Audible only
2) Audi & Visi
1) Audible only
Table 7.1: Programming features for UL864
Point programming
Each of the points in the system can be programmed with its own characteristics. Point
functions simplify the programming of points by allowing you to define a common set of
characteristics for similar points, and assigning those characteristics to selected points as a
point function. There are 16 point functions, each of which has programmable features for
configuration (fire, waterflow, and so on), local only operation, silencing, and loop response.
Each point is assigned to use the characteristics of one point function, and then is individually
programmed for additional characteristics: response to an open circuit, enabled status, output
zone, verification, latching and point description.
Before programming the control panel, determine the types of functions that are needed, and
then map the various input points to the functions. For example, you might determine that you
have the following functions:
1 = Pull Station
2 = Smoke Detector
3 = Reset Keyswitch
4 = Silence Keyswitch
5 = Supervisory Input
6 = Local Test
7 = Waterflow Sensor
For the characteristics that correlate with each function, see the following table. For default
point function information, see Appendix D.
7.2
50
en | Programming
Fire Alarm Control Panels
2012.08 | 04 | F01U008458
Installation and Operation Manual
Bosch Security System, Inc.