Bosch FPD-7024 User Manual

Page of 122
PIN Authority Level
Allowed Operations
Maximum (1)
All control panel operations, including
programming and disable.
Medium (2)
System test modes, fire drill, reset, silence,
view history.
Minimum (3)
Silence, view history.
None (0)
None.
Table 8.1: PIN authority levels
The following window appears:
AUTHORITY
USER (01 - 15)
Enter the user for whom you want to program the authority level and press [#/Enter]. The
following window appears and scrolls through the following choices:
USER 1 ATHRY (_______ )
0- NONE
1- MAXIMUM
2- MEDIUM
3- MINIMUM
Press the number key that corresponds to your selection. The existing setting is shown in
parentheses on the first line. After you have programmed the user authority, the previous
window appears.
PROG SYSTEM
PROG SYSTEM
1 - (reserved)
2 - TIMERS
3 - AC LINE SYNC
4 - OPTION BUS
5 - PIN REQURED?
6 – NAC SIL MODE
7 - REMOTE PGM
Program timers
Shortcut: 0-PROG, 3-PROG SYSTEM, 2-TIMERS
The following window appears:
TIMERS
1 - SMOKE RESET
2 - AC FAIL DLY
3 - AUTO SILENCE
4 - (reserved)
5 - DISPLAY RATE
Smoke reset
Shortcut: 0-PROG, 3-PROG SYSTEM, 2-TIMERS
8.3
8.3.1
62
en | Control Panel Programming
Fire Alarm Control Panels
2012.08 | 04 | F01U008458
Installation and Operation Manual
Bosch Security System, Inc.