Remote programming
Shortcut: 0-PROG, 3-PROG SYSTEM, 7-REMOTE PGM
Remote programming allows the panel to be called from a remote site by phone to reconfigure
any of the programmable options. When remote programming is disabled, you can still
connect to the control panel for diagnostics and to view the existing program. PIN numbers
are suppressed while remote programming is disabled.
REMOTE PGM
0- DISABLE
1- ENABLE
Press [0/Prog] to select DISABLE or [1] to select ENABLE, and the previous window appears.
Danger!
After any programming change, and especially after remote program changes, completely
check operation of the control units. Hazards to life and property can result if the system is
not tested for incorrect programming.
 
PROG INPUTS
PROG INPUTS
1- POINT NUMBER
2- POINT FUNCT
3- POINT COPY
i
Notice!
Point functions allow quick programming of similarly functioning points (for example, pull sta-
tions, smoke detectors) with common settings.
 
For more information on point functions, see Point function, 70.
Point number
Shortcut: 0-PROG, 4-PROG INPUTS, 1-POINT NUMBER
POINT NUMBER (1-255):_____
Enter the point number you wish to program and press [#/Enter]. Once you have entered the
point number, the display scrolls through the following PROG INPUT options:
PROG POINT
0- FUNCTION
1- ALARM/TROUBL
2- OUTPUT ZONE
3- VERIFICATION
4- LATCHING
5- DESCRIPTION
<DRILL> NEXT PNT
<HIST> PREV PNT
Press the number key that corresponds to your selection.