Bosch FPD-7024 User Manual

Page of 122
PROGRAM MUX
1- MUX EDIT
2- MUX PROGRAM
3- BUS TYPE
4- AUTO PROGRAM
MUX Edit
Shortcut: 0-PROG, 9-PROGRAM MUX, 1- MUX EDIT
To add MUX devices to the system, use the MUX Edit option. Each device must have a unique
address programmed using the address switches.
The following window appears:
DEVICE TYPE ( )
0- NO DEVICE
2- SINGLE INPUT
3- I/O MODULE
4- MUX SMOKE
5- SMOKE W/FRZ
6- DUAL INPUT
7- OCTAL INPUT
DescriptionModel
0- NO DEVICE
2- SINGLE INPUT D7044/M, D7045, FMM-7045, D7052(Class A)
3- I/O MODULE D7053
4- MUX SMOKE D7050, D7050TH, D343
5- SMOKE W/FRZ Not Used
6- DUAL INPUT D7052(Class B)
7- OCTAL INPUT D7042
Press the number that corresponds with the device you are adding or press [0/Prog] if you are
removing a device. When the device type is selected, the following window appears:
POINT NUMBER
(009 - 255) 009
Enter the address of the point being added, and press [#/Enter]. The device type window
appears again allowing additional devices to be added. Eight points are added at once when
the D7042 is added to the control panel.
MUX Program
Shortcut: 0-PROG, 9-PROGRAM MUX, 2-MUX PROGRAM
To add MUX devices to the system simultaneously while programming an address into the
device itself, use the MUX Program option. This programs a specified address into the device,
and also sets the control panel to use the device.
!
Warning!
Programming issues!
The D7042 is programmed using switches and cannot be added using the MUX Program fea-
ture. Use MUX Edit instead.
All devices must be removed from MUX bus A before programming by removing power from
the system, disconnecting the wires to the field devices, and re-powering the system. Failure
to disconnect devices results in all devices on loop A being programmed to the new address.
 
All programming is performed on Bus A, including addresses 129 to 255 that can only be
installed on Bus B for operation. Be sure to connect devices with addresses 129 to 255 to
Bus B, not to Bus A.
8.9.1
8.9.2
 
90
en | Control Panel Programming
Fire Alarm Control Panels
2012.08 | 04 | F01U008458
Installation and Operation Manual
Bosch Security System, Inc.