Bosch FPD-7024 User Manual

Page of 122
3
Point is at an illegal address
The addresses at which multi-address devices
can be installed are restricted.
4
Too many multiplex relays
Only 20 input output devices can be supported
on a given bus.
Table 8.7: Auto programming error messages
For details on installation restrictions, see also the specific device’s installation instructions
When the point adding operation completes, the FPD‑7024 shows for five seconds the total
number of points that were added to the control panel. Confirm that the number of devices
added matches the expected number.
AUTO PROGRAM
xxx POINTS ADDED
!
Warning!
Undetected devices!
If a new device is not detected on the bus during the point adding operation, the device does
not operate and does not generate trouble conditions even if it remains connected to the bus.
 
When the point adding operation completes, the display shows the total number of points on
the system:
AUTO PROGRAM
xxx MUX POINT
Note that xxx is the total number of points, not devices.
Confirm that the system shows the exact number of points expected. Points that are not
included in the total count do not operate and do not generate trouble conditions.
After the count of total points appears for approximately 10 sec, the FPD‑7024 restores the
multiplex system to normal operation. This process takes approximately 50 sec and the
following message appears during the restoral process:
AUTO PROGRAM
RESTORING
PLEASE WAIT...
!
Warning!
Test for proper operation!
As with any programming change to a system, test the system for proper operation before re-
turning it to service. At least test each added multiplex point after auto programming com-
pletes. Test according to NFPA 72.
 
Removing MUX Devices
 
Shortcut: 0-PROG, 9-PROGRAM MUX, 1- MUX EDIT
To remove a previously programmed multiplex device, use the MUX Edit feature.
 
 
8.9.5
96
en | Control Panel Programming
Fire Alarm Control Panels
2012.08 | 04 | F01U008458
Installation and Operation Manual
Bosch Security System, Inc.