System Sensor 1400 User Manual

Page of 4
D400-07-00                                                                                              1                                                                                              I56-279-05R
1400 Direct Wire Ionization
Smoke Detector
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Before Installing 
Please  thoroughly  read  the  System  Sensor  manual  A05-
1003, Applications Guide for System Smoke Detectors. This 
manual provides detailed information on detector spacing, 
placement, zoning, wiring, and special applications. Copies 
of  this  manual  are  available  at  no  charge  from  System 
Sensor.  (For  installation  in  Canada,  refer  to  CAN/ULC-
S524,  Standard  for  the  Installation  of  Fire  Alarm  Systems 
and CEC Part 1, Sec. 32.)
General Description
System Sensor 1400 dual-chamber ionization smoke detec-
tors  utilize  state-of-the-art,  unipolar  sensing  chambers. 
These detectors are designed to provide open area protec-
tion, and to be used with compatible UL-listed, 2-wire con-
trol  panels  only.  The  detector’s  operation  and  sensitivity 
can be tested in place.
Specifications
Diameter:                                       5.5 inches (140 mm)
Height:                                          3.12 inches (80 mm)
Weight:                                          0.7 lb. (310 g)
Operating Temperature:                  0°C to +49°C (32°F to 120°F)
Latching Alarm:                             Reset by momentary power interruption.
Operating Humidity:                       10% to 93% Relative Humidity, Noncondensing
Electrical Ratings:
System Voltage:                              12/24 VDC
Maximum Ripple Voltage:               4 Volts peak to peak
Start-up Capacitance:                      0.02 µA Maximum
Standby Ratings:                            8.5 VDC Minimum
                                                     35 VDC Maximum
                                                     100 µA Maximum
Alarm Ratings:                               4.2 VDC Minimum at 10 mA
                                                     6.6 VDC Minimum at 100 mA
                                                     Alarm current must be limited to 100 mA maximum by the control panel. If used, the 
RA400Z Remote Annunciator operates within the specified detector alarm currents.
Reset Voltage:                                 2.5 VDC Minimum
Reset Time:                                    0.3 S Maximum
Start-up Time:                                35 S Maximum
Each detector includes an LED that provides a local visual 
indication  of  the  detector’s  status.  The  LED  blinks  every 
ten seconds as an indication that power is applied to the 
detector and lights continuously in alarm. These detectors 
also have the latching alarm feature. The alarm can be reset 
only by a momentary power interruption.
The  detector  also  has  provision  for  the  connection  of  an 
optional Model RA400Z Remote Annunciator. The RA400Z 
provides a visual indication of an alarm and mounts to a 
single gang box.
Spacing
NFPA  72  defines  the  spacing  requirements  for  smoke 
detectors. Typically, this is 30 feet when the detectors are 
installed  on  a  smooth  ceiling.  However,  ALL  installations 
must comply with NFPA 72 and/or special requirements of 
the authority having jurisdiction.