System Sensor DH100ACDCLP User Manual

Page of 8
D200-14-00                                                                                              1                                                                                            I56-0084-08R
DH100ACDCLP Air Duct Smoke Detector 
with Extended Air Speed Range
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
 3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
The  Innovair  DH100ACDCLP  model  is  a  photoelectric 
detector approved for an extended air speed range of 100 to 
4000 feet per minute (0.5 m/s to 20.3 m/s) and an opera-
tional temperature range of 32°F to 131°F (0°C to 55°C).
Before Installing
Please thoroughly read the System Sensor Guide for Proper 
Use  of  Smoke  Detectors  in  Duct  Applications
  (A05-1004), 
which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of this manual are available online at www.systemsensor.com 
or via System Sensor’s toll free fax-back service, Documents 
on Demand at 800/736-7672. NFPA Standards 72 and 90A 
should also be referenced for detailed information. 
NOTICE: This manual shall be left with the owner/user of 
this equipment.
IMPORTANT: This detector must be tested and maintained 
regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.
Table of Contents                                                 Page
[1] General Description........................................................ 1
[2] Limitations of Duct Smoke Detectors...............................1
[3] Exploded View of Duct Smoke Detector Components......2
[4] Contents of the Duct Smoke Detector Kit.........................2
[5] Installation Sequence.......................................................2
[6] Duct Smoke Detector Maintenance and Test Procedures ..5
[7] Detector Cleaning Procedures..........................................7
[8] Board Replacement .........................................................8
[9] Specifications ..................................................................8
Warranty ..............................................................................8
[1] General Description
An HVAC system supplies conditioned air to virtually every 
area  of  a  building.  Smoke  introduced  into  this  air  duct 
system will be distributed throughout the entire building. 
Smoke  detectors  designed  for  use  in  air  duct  systems  are 
used to sense the presence of smoke in the duct. 
Model  DH100ACDCLP  Air  Duct  Smoke  Detector  utilizes 
photoelectric  technology  for  the  detection  of  smoke.  This 
detection method, when combined with an efficient hous-
ing design, samples air passing through the duct and allows 
detection of a developing hazardous condition. When suf-
ficient  smoke  is  sensed,  an  alarm  signal  is  initiated  and 
appropriate action can be taken to shut off fans, blowers, 
change  over  air  handling  systems,  etc.  These  actions  can 
facilitate  the  management  of  toxic  smoke  and  fire  gases 
throughout the areas served by the duct system.
The  DH100ACDCLP  detector  is  designed  to  operate  on 
24  VDC/VAC,  120  VAC,  or  240  VAC.  Alarm  and  supervi-
sory relay contacts are available for control panel interface 
(alarm initiation), HVAC control, and other auxiliary func-
tions. Auxiliary relays are also provided for fan shut down 
or signaling of up to 9 other detectors in the loop for mul-
tiple  fan  shut  down.  These  detectors  are  not  designed  for 
2-wire applications.
For testing, the alarm can be enabled by a magnet activated 
test switch or by the optional remote test station. The duct 
smoke  detector  latches  into  alarm  state  when  an  alarm 
occurs. A green LED flashes to indicate power, a red LED 
signals  local  alarm  indication,  and  optional  accessories 
offer a variety of annunciation capabilities.
The  DH100ACDCLP  can  be  reset  by  a  momentary  power 
interruption,  the  reset  button  on  the  front  cover,  the  con-
trol panel, or remote reset accessory. The DH100ACDCLP 
incorporates  a  cover  tamper  feature  that  provides  a 
trouble  signal  after  7  minutes  if  the  cover  is  removed 
or  improperly  installed.
  Proper  installation  of  the  cover 
removes the trouble condition.
[2] Limitations Of Duct Smoke Detectors 
WARNING
The National Fire Protection Association has established that 
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE 
FOR OPEN AREA DETECTOR PROTECTION as a means of 
providing life safety. Nor are they a substitute for early warn-
ing in a building’s regular fire detection system.
System  Sensor  supports  this  position  and  strongly  recom-
mends that the user read NFPA Standards 90A, 72, and 101. 
The DH100ACDCLP Air Duct Smoke Detectors are listed per 
UL 268A.
WARNING
This device will not operate without electrical power. 
Fire situations may cause an interruption of power. The 
system safeguards should be discussed with your local 
fire protection specialist.
WARNING
This device will not sense smoke unless the ventilation 
system is operating and the cover is installed.
WARNING
For this detector to function properly, it MUST be installed 
according to the instructions in this manual. Furthermore, 
the detector MUST be operated within ALL electrical and 
environmental specifications listed in this manual. Failure 
to comply with these requirements may prevent the detec-
tor from activating when smoke is present in the air duct.