System Sensor DH100LP User Manual

Page of 8
D200-15-00                                                                                              1                                                                                            I56-0083-07R
DH100LP Air Duct Smoke Detector
with Extended Air Speed Range
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
 3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
The  Innovair  DH100LP  model  is  a  photoelectric  detector 
approved  for  an  extended  air  speed  range  of  100  to  4000 
feet per minute
 (0.5 m/s to 20.3 m/s) and has an opera-
tional temperature range of 32°F to 131°F (0°C to 55°C).
Before Installing
Please thoroughly read the System Sensor Guide for Proper 
Use  of  Smoke  Detectors  in  Duct  Applications
  (A05-1004), 
which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of this manual are available online at www.systemsensor.com 
or via System Sensor’s toll free fax-back service, Documents 
on Demand at 800/736-7672. NFPA Standards 72 and 90A 
should also be referenced for detailed information. 
NOTICE: This manual shall be left with the owner/user of 
this equipment.
IMPORTANT: This detector must be tested and maintained 
regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.
Table of Contents                                                 Page
[1]  General Description ...................................................  1
[2]  Limitations of Duct Smoke Detectors........................... 1
[3]  Exploded View of Duct Smoke Detector Components .. 2
[4]  Contents of the Duct Smoke Detector Kit..................... 2
[5]  Installation Sequence .................................................. 2
[6]  Duct Smoke Detector Maintenance
      and Test Procedures.................................................... 5
[7]  Detector Cleaning Procedures...................................... 7
[8]  Board Replacement..................................................... 7
[9]  Specifications.............................................................. 8
Warranty........................................................................... 8
[1] General Description
An HVAC system supplies conditioned air to virtually every 
area  of  a  building.  Smoke  introduced  into  this  air  duct 
system will be distributed throughout the entire building. 
Smoke  detectors  designed  for  use  in  air  duct  systems  are 
used to sense the presence of smoke in the duct. 
Model DH100LP Air Duct Smoke Detectors utilizes photo-
electric technology for the detection of smoke. This detec-
tion  method  when  combined  with  an  efficient  housing 
design  samples  air  passing  through  the  duct  and  allows 
detection of a developing hazardous condition. When suf-
ficient smoke is sensed, an alarm signal is initiated at the 
fire control panel monitoring the detector, and appropriate 
action can be taken to shut off fans, blowers, change over 
air handling systems, etc. These actions can facilitate the 
management of toxic smoke and fire gases throughout the 
areas served by the duct system.
DH100LP detectors are designed to operate with 12/24VDC 
UL listed compatible 2-wire control panels. Alarm current 
must  be  limited  to  130mA  or  less  by  the  control  panel. 
Auxiliary relay contacts for control purposes are not avail-
able for use with the DH100LP. Control must initiate from 
the control panel. 
 
For testing, the alarm can be enabled by a magnet activated 
test switch or by the optional remote test station. The duct 
smoke  detector  latches  into  alarm  state  when  an  alarm 
occurs. A green LED flashes to indicate power, a red LED 
signals  local  alarm  indication,  and  optional  accessories 
offer a variety of annunciation capabilities.
The DH100LP can be reset by a momentary power interrup-
tion, the reset button on the front cover, the control panel, 
or remote reset accessory. 
[2] Limitations Of Duct Smoke Detectors
WARNING
The  National  Fire  Protection  Association  has  established 
that  DUCT  DETECTORS  MUST  NOT  BE  USED  AS  A 
SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION 
as a means of providing life safety. Nor are they a substi-
tute for early warning in a building’s regular fire detection 
system.
System  Sensor  supports  this  position  and  strongly  recom-
mends that the user read NFPA Standards 90A, 72, and 101. 
The DH100LP Air Duct Smoke Detectors are listed per UL 
268A.
WARNING
This  device  will  not  operate  without  electrical  power. 
Fire  situations  may  cause  an  interruption  of  power.  The 
system safeguards should be discussed with your local fire 
protection specialist.
WARNING
This  device  will  not  sense  smoke  unless  the  ventilation 
system is operating and the cover is installed.