Fire alarm systems 
Heat detectors 
6275 and 6276 
•  Fixed temperature alarm level 
•  Latching 
•  Can be plugged in a conventional or an addressable base 
General 
The detectors are conventional fixed 
temperature heat detectors, i.e. they "give an 
alarm" at a certain fixed temperature. 
6275 goes into alarm at 60°C. 
6276 goes into alarm at 80°C. 
The detector's sensing element consists of a 
bimetal contact.  At the reached alarm 
temperature the bimetal makes contact and 
the detector "gives an alarm".  An LED, in 
the base the detector is plugged into, 
indicates this. The base also has an output 
for an external LED indicator 2216 / 2217. 
Latching 
The heat detectors are latching, i.e. the 
detectors will not be automatically reset if 
the temperature falls below the detector's 
"alarm temperature" (60
°C and 80°C 
respectively).  The detector will be latched 
and the LED in the base and an ext. LED 
will be lit until reset is performed in the 
c.i.e. 
Miscellaneous 
The detectors 6275 and 6276 can be plugged 
into a conventional base (2324) connected to 
a conventional zone line input (or an older 
addressable base (2330) connected to a 
COM loop). 
Product applications 
The heat detectors can be used in the 
systems EBL500 / 512 / 128 / 1000 / 2000. 
The detectors are intended for indoor use 
and in dry premises. 
Heat detector applications are small rooms 
where the temperature can be expected to 
rise rapidly in case of a fire or places where 
smoke detectors can not be used.