Panasonic 3309 Leaflet

Page of 2
 
 
 
Panasonic Electric Works Fire & Security Technology Europe AB 
 
Jungmansgatan 12, SE-211 19 Malmö, Sweden 
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com 
 
Fire alarm systems 
Enclosed analog 
heat detector  
3309 
•  Different modes for compatibility with other EBL systems / detectors 
•  Algorithms for class A1, A2 S or B S 
• 
   
ATEX compliance 
•  Waterproof (IP67) 
General 
The analog heat detector 3309 measures the 
temperature through a thermistor.  The 
temperature range is 0
°C to 100°C in steps 
of 0.5
°C.  The detector has an LED that will 
light up when the detector goes into alarm.  
The detector also has an output for an 
external LED, e.g. 2218. 
Programming/Compatibility 
The address setting tool 3314 is used to set 
the detector's COM loop address.  The 
detector has an address label inside, where 
the address is to be written.   
 
3314 is also used to set the detector mode. 
•  NORMAL  mode (analog):  Used in the 
system EBL512 (SW version >2.0) and 
EBL128.  The detector works as a 
temperature sensor where the analog 
readings (0
°C to 100°C) are converted to 
digital "sensor values" that are read and 
evaluated by the c.i.e.  Algorithms for 
class A1, A2 S or B S (set in Win512).  
When the class A1 or A2 S algorithm is 
used, 3309 is a spare part for detector 
2340 and when the class B S algorithm is 
used, 3309 is a spare part for 2341. 
•  2330 mode (conventional):  Used in the 
systems EBL512 / 1000 / 2000 as an 
equivalent to the enclosed addressable 
fixed temperature heat detector 2340 
(60
°C), i.e. as a class A2 S heat detector 
(static response temperature 57
°C). 
•  2312 mode:  Not used for 3309. 
Algorithms 
EBL512 / EBL128 use algorithms for class 
A1, A2 S and B S, according to EN54-
5:2000, for fire alarm detection. Via Win512 
/ Win128 is an algorithm selected for each 
3309 in NORMAL mode. 
   
ATEX classification 
3309 complies with the ATEX classification 
Ex II 3GD EEx nA II T5.  
Waterproof 
The thermistor, the LED, all electronics, etc. 
is mounted in a waterproof detector housing, 
mounted on a connection box. 
Label holder 
A label holder, intended for a label showing 
"zone-address" or "technical number", can 
be mounted in the connection box. 
Miscellaneous 
The COM loop is connected to the detector, 
which is provided with three pairs of flying 
leads with female push-on connectors.   
Product applications 
Used in the systems EBL512 / 128 / 1000 / 
2000.  
Heat detectors are normally used where 
smoke detectors can not be used or in rooms 
where the temperature can be expected to 
rise rapidly in case of a fire. 
The detector is intended for outdoor use 
(must not be exposed to heavy sunlight) or 
in high humidity indoor premises.