Panasonic 6298 Leaflet

Page of 2
 
 
 
Panasonic Electric Works Fire & Security Technology Europe AB 
 
Jungmansgatan 12, SE-211 19 Malmö, Sweden 
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com 
 
Fire alarm systems 
Enclosed heat 
detectors 6295, 6296, 
6297 and 6298 
•  Fixed temperature alarm level 
• 
   
ATEX compliance 
•  Waterproof (IP67) 
Fixed temperature alarm level 
The detectors are conventional fixed 
temperature heat detectors, i.e. they will give 
an alarm within a response temperature 
range in accordance with EN54-5:2000. 
The sensing element is a heat pick-up shield 
and a bimetal switch. 
An LED on the detector (not on 6298) will 
light up when the detector goes into alarm.  
The detector also has an output for an 
external LED 2216 / 2217. 
The following types are available (static 
response temperature, class & EN54-5 temp. 
range): 
6295, 57
°C, class A2 S (54 to 70°C). 
6296, 72
°C, class B S (69 to 85°C). 
6297, 87
°C, class C S (84 to 100°C). 
6298, 117
°C, class E S (114 to 130°C). 
Latching 
The detectors are latching, i.e. they will not 
be automatically reset if the temperature, 
after the alarm, falls below the detector's 
static response temperature.  The detector's 
LED and a connected ext. LED will be lit 
until the detector is reset via the c.i.e. 
   
ATEX classification 
The detectors 6295 and 6296 complies with 
the ATEX classification Ex II 3GD EEx nA 
II T5
.  See also the opposite side of this 
page. 
 
Waterproof connection box 
The heat pick-up shield, the LED, all 
electronics, etc. are mounted in a grey water-
proof detector housing, to be mounted on the 
attached connection box, which has three 
cable inlets.  Three compression glands and 
a silicon gasket for IP67 are also attached. 
Label holder 
A label holder intended for a label showing 
"zone number", can be mounted in the 
connection box. 
Miscellaneous 
The detectors 6295-6298 are provided with 
three pairs of flying leads with female push-
on connectors, see figure on the opposite 
side of this page.  (Zone line cables (in / out) 
and an external LED.) 
Product applications 
The detectors can be used in the systems 
EBL500 / 512 / 128 / 1000 / 2000 provided 
with some zone line inputs for the system 
respectively (e.g. an 8 zones expansion 
board 1580 / 4580 input, an addressable 
zone interface 2226 / 2335 input, an 
addressable multi purpose I/O unit 3361 
input, etc.). 
Heat detectors are normally used in rooms 
where the temperature can be expected to 
rise rapidly in case of a fire or places where 
smoke detectors can not be used. 
The detectors are intended for outdoor use or 
indoor use in high humidity premises.