IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide
– 12 –
RF Specifications
Frequency Bands
2G
2G
GSM/GPRS/EDGE
Quad Band, 850/900/1800/1900 MHz
3G/4G
UMTS/HSPA+
Band V, Band II
Output Power
2G
2G
GPRS
+33dBm, GMSK modulation
EDGE
+27dBm, 8-PSK modulation
3G
UMTS
+24dBm, QPSK modulation
WCDMA
+24dBm, QPSK modulation
4G
HSPA+
+24dBm, 64 QAM modulation
WCDMA
+24dBm, 64 QAM modulation
Central Station Messages
Alarm Condition
Alarm Code
Restore Code
Power On / Reset
E339 C0803
N/A
ECP Supervision (Compromise Indication)
E355 C0000
R355 C0000
Primary Communication Path Supervision
E350 C0951
R350 C0951
Secondary Communication Path Supervision
E350 C0952
R350 C0952
Periodic GSM Comm Path Test Failure
(We do not send a restoral R358 C0803, we send a failure message every day after
the radio attempts to test and fails.)
the radio attempts to test and fails.)
E358 C0803
N/A
Trouble Reporting:
When a single fault (open or short IP, GSM suppression, low/missing battery,
AC loss) occurs, and the communicator is programmed for an IP& GSM
communication path, multiple alarm Codes and their appropriate Restore
Codes are reported to the Central Station.
When a single fault (open or short IP, GSM suppression, low/missing battery,
AC loss) occurs, and the communicator is programmed for an IP& GSM
communication path, multiple alarm Codes and their appropriate Restore
Codes are reported to the Central Station.
IPGSM-4GC communicator fault – The Fire Panel sends out a E380, and E352
message via Telco #1, these are then relayed to the central station via the
IPGSM-4GC.
message via Telco #1, these are then relayed to the central station via the
IPGSM-4GC.
Telco line 1 fault – The Fire Panel sends out a E380, and E351 message via
Telco #2, these are then relayed to the central station via the IPGSM-4GC.
Telco #2, these are then relayed to the central station via the IPGSM-4GC.
Telco line 2 fault - - Fire Panel sends out a E380, and E352 via Telco #1,
these are then relayed to the central station via the IPGSM-4GC.
E380, E351, E352
codes as
codes as
appropriate.
N/A
Test
5555 5555 9
N/A
Specific to COMMERCIAL Control Panels (Such as the VISTA-32FB, and VISTA-128FBP/250FBP series.)
Communicator Trouble (low battery, ECP bus, network) (Possible
Compromise Indication)
Communicator Trouble (low battery, ECP bus, network) (Possible
Compromise Indication)
E333 C0803
R333 C0803
Radio Loss of Signal
(Possible Compromise Indication)
E357 C0803
R357 C0803 or
R380 C0803
Radio Fault (low battery, tamper, ECP Bus)
E333 C0803
R333 C0803
AlarmNet Messages
Communication failure.
(Possible Compromise Indication)
Communication failure.
(Possible Compromise Indication)
5555 1555 6
5555 3555 6
Authorized Radio Substitution
00D0 010C 0
N/A
Unauthorized Radio Substitution Attempt
00D0 010E 0
N/A
Service Termination
00D0 020E 0
N/A