First Alert SA320CN Leaflet

Page of 2
firstalert.com
ARCHITECTURAL  AND ENGINEERING SPEC 
INSTALLATION OF ALARM
The smoke alarm shall be a First Alert Model SA320 and shall provide at a minimum the 
following features and functions:
  1.  Two smoke sensing chambers - photoelectric and ionization.
  2.  Powered by two AA alkaline batteries and have a solid state piezo horn rated at  
 
 85dB at 10 ft. and shall be capable of self restoring.
  3.  A visual power-on indicator to confirm unit is receiving power. 
  4.  Two Latching features: Alarm Latch to easily identify initiating alarm after alarm  
 
 condition has subsided. Low battery latch: to visually identify which unit is in low  
 
 battery condition. Two Silence Features: Alarm Silence to temporarily silence  
 
 nuisance alarms. Low Battery Silence to silence low battery chirp for up to 8 hours.
   5.  Two Locking features - tamper resistant locking pins that lock battery drawer  
 
 and/or alarm to mounting bracket.
  6.  The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and  
 
 relative humidity between 10% and 95%.
  7.  The unit shall contain mounting hardware and shall be listed for wall or ceiling  
 
 mounting.
  8.  The unit shall have a gasketless base for easy installation and be capable of  
 
 keeping alarm secure over a wide rotation range to allow for true alarm
 
 alignment.
  9. The unit shall at a minimum meet the requirements of UL217, CSFM, 
 
 NFPA 72 and the ICC.
SHIPPING SPECS:
TECHNICAL  SPECS
Individual Carton Dimensions  
2.5"L x 7.0"W x 8.5"H
 .
s
b
3
7
.
0
  
t
h
g
i
e
W
  
 
4
 
8
3
7
0
0
 
4
5
0
9
2
 
0
  
C
P
U
  
 
Master Carton Dimensions  
7.7"L x 7.31"W x 9.06"H
Master Pack 
3
.
s
b
l
 
.28
2
  
t
h
g
i
e
W
  
 
300 29054 00738 5
  
:
5
f
o
2
  
Pallet Information  
   Cases per Layer 
30
   Number of Layers:  
5
   Cases per Pallet:  
150
   Units per pallet: 
450
.
s
b
350 
  
:t
h
g
i
e
W
  
 
©2011 BRK Brands, Inc. a Jarden Corporation 
Company (NYSE: JAH)
3901 Liberty Street Road
Aurora, IL  60504-8122
All rights reserved
First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM3044
CAT. 
SA320CN
BATTERY DRAWER LOCK
 
Remove Pin from 
Mounting Bracket
 
Close Door. Insert Pin in Holes 
through alarm and Battery Drawer
5.0"
TOP VIEW
SIDE VIEW
MOUNTING
BRACKET
2.0"
THE PARTS OF THIS SMOKE ALARM
 
 
BOTTOM OF ALARM
  1.   Mounting bracket
  2.   Mounting Slots
  3.   Battery Drawer - Install
 
  2 AA batteries here
  4.   Turn this way to 
 
  remove from bracket
   5.   Turn this way to 
 
  attach to bracket
 
 
TOP OF ALARM
  1.   Test/Silence button
  2.   Slide-open
 
  battery drawer
  3.   Power/Alarm light
 
 
 
Alarm Dimensions:  
5.0” dia x 2.0”H
Weight:  
8.6 oz
Operating Voltage:  
Two 1.5V AA alkaline batteries
Temperature Range:   40°F (4°C) to 100°F (38°C)
Humidity Range: 
10% to 95% relative humidity (RH)
Audio Alarm: 
85dB at 10 feet
Test/Silence: 
Electronically simulates smoke condition, causing the unit  
 
to alarm. Press and hold test/silence button
Alarm Reset: 
Automatic when smoke clears
Smoke Sensors: 
Photoelectric and Ionization
Indicator Lights/Sounds:
   DC Power:  
Intermittent Green LED
   Local Alarm:  
Red LED flashes rapidly
   Alarm Latch:  
LED flashes red 2 sec on, 2 sec off after local alarm stops
   Low Battery Latch: 
LED flashes green 2 sec on, 2 sec off
Listing: 
Listed to UL217 Standard