Kidde i12060 Leaflet

Page of 2
Architectural and Engineering
Specifications
 
The smoke alarm shall be Kidde Model i12060 or approved equal.  
It shall be powered by a 120VAC, 60Hz source along with a 9V battery
backup. The unit shall incorporate an ionization sensor with nominal  
sensitivity of 0.50 to 1.06%/ft. The temperature operating range shall  
be between 40°F and 100°F (4°C and 38°C) and the humidity operating
range shall be 5% - 95% relative humidity.
 
The smoke alarm can be installed on any standard single gang  
electrical box, up to a 4” octagon junction box. The electrical connection
(to the alarm) shall be made with a plug-in connector. A maximum of 
24 Kidde devices can be interconnected in a multiple station arrange-
ment. The interconnect system must not exceed the NFPA (National Fire
Protection Association) limit of 18 initiating devices, of which 12 can  
be smoke alarms. With 18 initiating devices (Smoke, heat, CO, etc),  
interconnected, it is still possible to interconnect 6 strobe lights and/or 
relay modules. The alarm shall provide optional tamper resistance that 
deters removal of the unit from the wall or ceiling and locks the battery 
door closed. No additional pieces shall be required to activate this feature.
 
The alarm shall include an easy access battery compartment that is 
opened and closed by pressing on the battery door. The 9V battery carrier 
will ensure proper battery backup protection by not allowing the battery 
door to close if the battery is placed in the unit incorrectly or if a battery 
is not present. The unit shall also provide an optional tamper resistant 
switch that will prevent the battery door from being opened.
The unit shall include a piezoelectric horn that is rated at 85  
decibels at 10 feet. The unit shall include the Smart Hush
TM
 feature  
that silences the unit for approximately 7 minutes if a nuisance  
condition occurs. 
The unit shall incorporate red and green LED indicators. The green  
LED (when illuminated) indicates the presence of AC power. The red LED
(located under the TEST/Hush button) has
four modes of operation:
Standby Condition: The red LED will flash every 30-40 seconds to  
indicate that the smoke alarm is operating properly. 
Alarm Condition:  
When the alarm senses products of combustion and goes into alarm the 
red LED will flash one flash per second. The flashing LED and pulsating
alarm will continue until the air is cleared.When units are interconnected, 
only the red LED of the alarm that senses the smoke or is being tested
(the originating unit) will flash.  All other units in the interconnected  
system will sound an alarm but their red LED’s will NOT flash.
Alarm 
Memory:  This smoke alarm is equipped with an alarm memory, which 
provides a visual indication when an alarm has been activated.  The red 
LED will illuminate for about 1.5 seconds every 16 seconds to indicate  
the memory condition. 
Smart Hush
TM
 Mode:  The red LED will illuminate
for 1.5 seconds every 8 seconds, indicating the smoke alarm is in the  
Smart Hush
TM
 Mode. 
 
The unit shall at a minimum meet the requirements of UL217, 
NFPA72, and (chapter 11), The State of California Fire Marshall, NFPA101
(0ne and two family dwellings), Federal Housing Authority (FHA), Housing
and Urban Development (HUD).
120V AC/DC Wire-in Smoke Alarm
Front Battery Door
Part# 21006376
Model i12060
Technical Specifications
Model: 
i12060
Power Source:
120VAC (
80mA),
60HZ, 9V battery backup
Audio Alarm:
85dB at 10ft
Temperature Range:  40˚F to 100˚F (4˚C to38˚C)
Humidity Range:
5%-95% relative humidity (RH)
Sensor:
Ionization
Size:
5” in diameter x 1.75” depth
Weight: 
.5lbs
Interconnects:
Up to 24 Kidde devices
LED:
Green, receiving AC power
Red, 4 modes of operation
Warranty: 
10 year limited warranty
Installation of Smoke Alarm
The smoke alarm should be installed to comply with all local codes having jurisdiction
in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all
alarms are wired to a single, continuous (non-switched) power line, which is not pro-
tected by a ground fault interrupter. A maximum of 1000 ft. of wire can be used in 
the interconnect system. Use standard UL listed household wire as required by code.
FUSE OR CIRCUIT BREAKER
BLACK
WHITE
RED
L
N
First 
Alarm
Additional 
Alarms
Ordering Information
Ordering  
 
 
 
Dimensions 
 
Case/ 
Layers/   
Skid  
Number 
UPC 
I2F5 
Pack Quantity 
(w x d x h inches)  Weight  Skid 
Skid 
Weight 
N/A
7-84908-00135-1  N/A
individual*
5.75 x 1.5 x 5.75  0.5 lbs  N/A
N/A
N/A
21006376
7-84908-00135-1  107-84908-00135-8
Cut Case (6 units)
6.5 x 13.25 x 6
3 lbs
147
7
441 lbs
21005927
0-47871-05927-0  200-47871-05927-4
Bulk Pack (6 units)
6 x 10.5 x 6
3 lbs
147
7
441 lbs
21006932
7-84908-00135-1  407-84908-00135-9
Bulk Pack (36 units)
19.5 x 11.75 x 12  18 lbs
24
4
432 lbs.
21006933
7-84908-00135-1  307-84908-00135-2
Display Pallet (36 units)  20 x 24 x 40
20 lbs.  4
1
90 lbs.
21005928
0-47871-27689-9  100-47871-27689-6
Cut Case (3 Twin Packs)  6.5 x 13.25 x 6
3 lbs
147
7
441 lbs
Alk. Btry 21006931
0-47871-27695-0  100-47871-27695-7
Cut Case (6 units)
6.5 x 13.25 x 6
3 lbs
147
7
441 lbs
*Not for sale by individual unit
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-i12060 sheet 
rev. 01-2009