Emerson Series 3000 MVD User Manual

Page of 348
Configuration and Use Manual
247
Specifications – Model 3300 and Model 3500
Dia
g
nostics and T
roub
leshooting
Spe
c
ifica
tions – Model 
3
350
/3
7
0
0
Specific
a
tions
 –
 Model 
330
0
/3
500
Measure
ment P
e
rf
or
mance
Discrete inputs
Two discrete, momentary inputs
Pulse width: 0.15 sec minimum
Voltage: 0–0.8 VDC low state, 3–30 VDC high state, dry contacts
A.6.3
Non-intrinsically safe output signals
Milliamp outputs
Two active 4–20 mA outputs
Isolated to ±50 VDC from all other outputs and earth ground
Maximum load limit: 1000
Ω
Output is linear with process from 3.8 to 20.5 mA, per NAMUR NE43 (June 1994)
Discrete outputs
Three discrete outputs
Configurable for the application
Polarity: Active high or active low, software selectable
Power: Internal pull-up to 24 V
Voltage: 24 VDC nominal
Current: Sourcing at 5.6 mA when V
out
 = 3 VCD, sinking up to 500 mA at 30 VDC maximum
Frequency/pulse output
One 2-wire frequency/pulse output
Output is linear with flow rate to 12,500 Hz
Configurable unit of measure
Scalable to 10000 Hz
Pulse width: 50% duty cycle above 500 Hz, configurable for frequencies below 500 Hz
Power: Active or passive, software selectable
Polarity: Active high or active low, software selectable
Voltage: 24 VDC nominal, active; 30 VDC applied maximum, passive
Current: Sourcing, 10 mA at 3 VDC, active; sinking, 500 mA, active or passive
Fault output
When a fault is detected, outputs go to configured states. User can select high, low, last measured 
value, or internal zero. Milliamp outputs conform to NAMUR NE43 (June 1994).
High output limits can be configured from 21 to 24 mA for milliamp; 15,000 Hz for frequency
Low output limits can be configured from 1 to 3.6 mA for milliamp; 0 Hz for frequency
Last measured value is the last output for the process variable
Internal zero drives the milliamp and frequency outputs for process variables to zero values