I/O Wiring – Model 2400S Analog Transmitters
P
o
wer Su
ppl
y
I/O
 W
irin
g
 – DP 
an
DN
I/
O W
iri
n
g
 – AN
Be
fo
re
 Y
o
Begin
3.4.1
mA output wiring 
The wiring diagrams in this section are examples of proper wiring for the Model 2400S mA output. 
The following options are shown:
Internal power:
-
Basic mA output wiring – Figure 3-1
-
HART/analog single-loop wiring – Figure 3-2
External power:
-
Basic mA output wiring – Figure 3-3
-
HART/analog single-loop wiring – Figure 3-4
HART multidrop wiring, internal or external power – Figure 3-6
Note: If you plan to configure the transmitter to poll an external temperature or pressure device, you 
must wire the mA output to support HART communications. You may use either HART/analog 
single-loop wiring or HART multidrop wiring.
Figure 3-1
Basic mA output wiring – Internal power 
820 Ohm maximum
loop resistance
+
Note: Channel B (terminals 3 and 4) can also 
be configured this way.