Performing maintenance
90
Instruction manual GWV
15
s
6. Switch the electronic controller ON by setting the On/Off switch to position I.
The display will now show INTERNAL CHECK for about 10 seconds and 
go to the main menu.
7. Activate the 'ON mode' by going through the following steps:
-
Press the blue arrow once ( ) to position the cursor in front of ON and 
press . 
-
Confirm the START OPERATION by pressing 
.
8. If there is no heat demand, increase Tset
. Note the original setting. If there is no demand, draw some 
hot water off to create demand.
9. Check whether the heating cycle runs correctly
10. If you have adjusted T
set 
, return it to the original value
11. Carefully remove the sheeting from the front of the appliance.
12. Check the supply and burner pressures
 and adjust these where necessary.
13. Check that all components of the flue gas system are properly attached.
14. Check the pressure differential across the orifice plate of the pressure switch 
(see the table). If the pressure difference is too low, the flue gas outlet and 
air supply should be checked for blockages.
Pressure switch differential
15. Test the operation of the overflow valve of the protected cold supply set-up. 
The water should spurt out.
16. Test the overflow operation of the P-valve. The water should spurt out.
17. Check the drainage pipes from the discharge points of all valves and remove 
any scale deposits that may be present.
18. Drain
 the appliance.
INTERNAL CHECK
MENU
 »OFF
^ ON
È WEEK PROGRAM
Appliance
Observed pressure differential across the pressure switch 
(Pa)
GWV 120
> 66
GWV 150
> 75
GWV 200
> 92