Quantum 340-17ACW-134 User Manual

Page of 40
Owner’s Manual 
                                                                                                                Quantum  Energy  Technologies 
Document number: QDC0030PD-11                                                                                                                                                                              Page 36 of 40 
 
A.11: Technical Data For Service Personnel – SIAM Compressors – R134a 
Parameters 
150-08ACW-134 
270 & 340-11AC3-134 
340TIH-134 
340-17ACW-134 
Superheat setting 
1.5Turn(F.Close) 
3.5 Turns(7 Turns ) F..Open 
3.5Turns(7Turns) F.Open 
TX valve + orifice size 
TI-E 2# 
TEN2 # 3(AAE 2MC) 
TEN2 # 4 
Winding Resistance @20℃  
C-R: 
2.13Ω, C-S: 3.91Ω C-R: 
0.96Ω, C-S: 1.77Ω 
Run Capacitor 
30μF (+10, -5%) 370 VAC 
30μF (+10, -5%) 370 VAC 
60μF (+0, -15%) 400 VAC 
Rated power supply 
220-240VAC, 50Hz 
220-240VAC, 50Hz 
220-240VAC, 50Hz 
Rated circuit breaker 
1Φ, 15A 
1Φ, 15A 
1Φ, 15A 
De-ice control setting 
On-5℃, Off + 8℃  (Timed De Icing) On - 5℃, Off + 8℃ (Timed De Icing) On-5℃, Off + 8℃  (Timed De Icing) 
Liquid injection capillary 
Eyre: ID 1.1mm x 1.5m 
Eyre: ID 1.1mm x 2.9m 
ID 1.1mm x 2m 
Liquid injection thermostat 
On at 85℃, Off at 75℃ 
On at 85℃, Off at 75℃ 
On at 85℃, Off at 75℃ 
Water temperature setting 
55℃/5℃ (Del. ≥60℃) 55℃/5℃ (Del. ≥60℃)  
55℃/5℃ (Del. ≥60℃) 
Refrigerant charge 
1650g 
1850g 
2650g 
Thermal cut-out setting 
105℃, manual reset 
105℃, manual reset 
105℃, manual reset