State Industries SBD85500PE User Manual

Page of 52
11
Breathing Hazard - Carbon Monoxide Gas
Breathing carbon  monoxide can cause brain  damage or
death.  Always read and understand  instruction  manual.
Under no circumstances should
the input exceed the rate shown
on the water heater’s rating label. 
Overfiring could result in damage to
the water heater and sooting.
Gas and carbon monoxide detectors
are available.
propane installations
INSTALLATIONS ABOVE 2000 FEET (610 METERS) REQUIRE 
REPLACEMENT oF BURNER oRIFICEs IN ACCoRDANCE 
WITh  CURRENT EDITIoN oF ThE NATIoNAL FUEL GAs CoDE 
(ANSI  Z223.1).  FOR  CANADIAN  INSTALLATIONS  CONSULT 
CANADIAN INSTALLATIONS CODE CAN/CSA B149.1. FAILURE 
To REPLACE oRIFICEs WILL REsULT IN IMPRoPER AND 
INEFFICIENT oPERATIoN oF ThE APPLIANCE REsULTING 
IN ThE PRoDUCTIoN oF INCREAsED LEVELs oF CARBoN 
MoNoXIDE GAs IN EXCEss oF sAFE LIMITs WhICh CoULD 
RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
You should contact your gas supplier for any specific changes 
which may be required in your area.
As elevation above sea level is increased, there is less oxygen 
per  cubic  foot  of  air.  Therefore,  the  heater  input  rate  should 
be reduced at high altitudes for satisfactory operation with the 
reduced  oxygen  supply.  Failure  to  make  this  reduction  would 
result  in  an  over  firing  of  the  heater  causing  sooting,  poor 
combustion and/or unsatisfactory heater performance.
Ratings specified by manufacturers for most appliances apply for 
elevations up to 2000 feet (610m). For elevations above 2000 feet 
(610), ratings must be reduced at the rate of 4% for each 1000 
feet (305m) above sea level. For example, if a heater is rated at 
78,000 Btuh (22.9 Kwh) at sea level, to rate the heater at 4000 feet 
(1219m), you subtract 4 (once for each thousand feet) x.04 (4% 
input reduction) x 78,000 (original rating) from the original rating.
Therefore, to calculate the input rating at 4,000 feet (1219m): 4 x 
.04 x 78,000 = 12,480 Btuh (3.7 Kwh), 78,000 (22.9 Kwh) - 12,480 
(3.7 Kwh) = 65,520 Btuh (19.2 Kwh). At 6000 feet (1829m) the 
correct input rating should be 59,280 Btuh (17.4 Kwh).
natural gas installations
The natural gas fired version of the water heater covered by this 
manual is certified for use without modification for altitudes up to 
10,100 feet.
For  installations  above  10,100  feet  call  the  technical  support 
phone number listed on the back cover of this manual for further 
technical assistance. Call the local gas or utility company to verify 
Btu per cubic foot content before calling for technical assistance 
and have that information available.
Note: The actual firing rate of the water heater must not exceed 
the input rating on the water heater's rating label under any 
circumstances.
Note:  Due  to  the  input  rating  reduction  at  high  altitudes,  the 
output  rating  of  the  appliance  is  also  reduced  and  should  be 
compensated for in the sizing of the equipment for applications.
See  the  Circulation  Pump  Wiring  Diagrams  (Figure  8,  Figure 
9)  in  this  manual  for  electrical  hookup  information.  Install  in 
accordance  with  the  current  edition  of  the  National  Electrical 
Code, NFPA 70 or the Canadian Electrical Code, CSA C22.1.
All-bronze circulators are recommended for used with commercial 
water heaters.
Some circulating pumps are manufactured with sealed bearings 
and do not require further lubrication. Some circulating pumps 
must  be  periodically  oiled.  Refer  to  the  pump  manufacturer’s 
instructions for lubrication requirements.
CIRCULATING PUMP WIRING DIAGRAM
STORAGE TANK OR BUILDING RECIRCULATION
FIELD SUPPLIED TEMPERATURE CONTROL
INSTALLED IN THE STORAGE TANK
OR CIRCULATING LOOP RETURN LINE
CIRC
PUMP
MOTOR
L1 HOT
L2 NEUTRAL
120 VAC
POWER
NOTE: USE SEPARATE 120 VAC POWER
SUPPLY FOR PUMP CIRCUIT. DO NOT
SHARE POWER WITH APPLIANCE AS THIS
MAY CAUSE ELECTRICAL LINE NOISE AND
LEAD TO ERRATIC CONTROL SYSTEM
OPERATION. 
CIRCULATING PUMP WIRING DIAGRAM
DISHWASHER LOOP WITH TOGGLE SWITCH
FIELD SUPPLIED TEMPERATURE
CONTROL INSTALLED IN THE
CIRCULATING LOOP RETURN LINE
DISHWASHER
TOGGLE
SWITCH
CIRC
PUMP
MOTOR
L1 HOT
L2 NEUTRAL
120 VAC
POWER
NOTE: USE SEPARATE 120 VAC POWER
SUPPLY FOR PUMP CIRCUIT. DO NOT
SHARE POWER WITH APPLIANCE AS THIS
MAY CAUSE ELECTRICAL LINE NOISE AND
LEAD TO ERRATIC CONTROL SYSTEM
OPERATION. 
figure 8.
CIRCULATING PUMP WIRING DIAGRAM
STORAGE TANK OR BUILDING RECIRCULATION
FIELD SUPPLIED TEMPERATURE CONTROL
INSTALLED IN THE STORAGE TANK
OR CIRCULATING LOOP RETURN LINE
CIRC
PUMP
MOTOR
L1 HOT
L2 NEUTRAL
120 VAC
POWER
NOTE: USE SEPARATE 120 VAC POWER
SUPPLY FOR PUMP CIRCUIT. DO NOT
SHARE POWER WITH APPLIANCE AS THIS
MAY CAUSE ELECTRICAL LINE NOISE AND
LEAD TO ERRATIC CONTROL SYSTEM
OPERATION. 
CIRCULATING PUMP WIRING DIAGRAM
DISHWASHER LOOP WITH TOGGLE SWITCH
FIELD SUPPLIED TEMPERATURE
CONTROL INSTALLED IN THE
CIRCULATING LOOP RETURN LINE
DISHWASHER
TOGGLE
SWITCH
CIRC
PUMP
MOTOR
L1 HOT
L2 NEUTRAL
120 VAC
POWER
NOTE: USE SEPARATE 120 VAC POWER
SUPPLY FOR PUMP CIRCUIT. DO NOT
SHARE POWER WITH APPLIANCE AS THIS
MAY CAUSE ELECTRICAL LINE NOISE AND
LEAD TO ERRATIC CONTROL SYSTEM
OPERATION. 
figure 9.
high altitude installations
Fire and Explosion Hazard
Gas and carbon monoxide detectors are
available.
Overfiring could result in fire or
explosion.
Under no circumstances should the 
input exceed the rate shown on the 
water heater’s rating label.