State Industries GS6 50 YBRT Series 201 User Manual

Page of 36
14
Align the legs of the draft hood with the slots provided. 
Insert the legs and secure the draft hood to the water 
heater’s top with the four screws provided as shown in 
Figure 9. Do not alter the draft hood in any way. If you are 
replacing an existing water heater, be sure to use the draft 
hood supplied with this water heater.
Vent Pipe Size                                                               
It is important that you follow the guidelines in these 
instructions for sizing a vent pipe system. If a transition 
to a larger vent size is required, the vent transition 
connection must be made at the draft hood outlet.
Vent Connectors                                                          
1.  Type B, Double wall, U.L. Listed Vent Pipe.
2.  Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum clearance 
from combustible materials when using type B double wall 
vent pipe.
Vent connectors made of type B, double wall vent pipe 
material may pass through walls or partitions constructed 
of combustible material if the minimum listed clearance is 
maintained.
Maintain a six inch minimum clearance from all 
combustible materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for 
water heaters located in attics and may not pass through 
attic spaces, crawl spaces or any confined or inaccessible 
location. A single wall metal vent connector cannot pass 
through any interior wall.
When installing a vent connector, please note the following 
(See Figures 10-12):
• 
Install the vent connector avoiding unnecessary bends, 
which create resistance to the flow of vent gases.
• 
Install without dips or sags with an upward slope of at 
least 1/4-inch per foot.
• 
Joints must be fastened by sheet metal screws or other 
approved means. It must be supported to maintain 
clearances and prevent separation of joints and 
damage.
• 
The length of the vent connector cannot exceed 75% of 
the vertical vent height.
• 
The vent connector must be accessible for cleaning, 
inspection, and replacement.
• 
Vent connectors cannot pass through any ceiling, floor, 
firewall, or fire partition.
• 
It is recommended (but not mandatory) that a minimum 
12 inches of vertical vent pipe be installed on the draft 
hood prior to any elbow in the vent system.
IMPORTANT: Existing vent systems must be inspected for 
obstructions, corrosion, and proper installation.
Chimney Connection                                                  
IMPORTANT: Before connecting a vent to a chimney, 
make sure the chimney passageway is clear and free of 
obstructions. The chimney must be cleaned if previously 
used for venting solid fuel appliances or fireplaces. Also 
consult local and state codes for proper chimney sizing 
and application or, in the absence of local and state 
codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 
54)-current edition.
• 
The connector must be installed above the extreme 
bottom of the chimney to prevent potentially blocking 
the flue gases.
• 
The connector must be firmly attached and sealed to 
prevent it from falling out.
• 
To aid in removing the connector, a thimble or slip joint 
may be used.
• 
The connector must not extend beyond the inner edge 
of the chimney as it may restrict the space between it 
and the opposite wall of the chimney (Figure 10).
LISTED LINED
CHIMNEY
2 FT. MINIMUM ABOVE ANY OBJECT 
WITHIN 10FT. HORIZONTALLY
DO NOT EXTEND 
VENT BEYOND EDGE
OF CHIMNEY
VENT
CONNECTOR
 
3 FT. MINIMUM
 
MAINTAIN
CLEARANCE*
SEAL 
SLOPE
UP 1/4 IN.
PER FT.
MINIMUM
CHIMNEY TERMINATION VENT SYSTEM
SUPPORT
STRAP
FIGURE 10.
Do not terminate the vent connector in a chimney that has 
not been certified for this purpose. Some local codes may 
prohibit the termination of vent connectors in a masonry 
chimney.
Vertical Exhaust Gas Vent                                          
Vertical exhaust gas vents must be installed with 
U.L. listed type B vent pipe according to the vent 
manufacturer’s instructions and the terms of its listing. 
It must be connected to the water heater’s draft hood by a 
listed vent connector or by directly originating at the draft 
hood opening.
Vertical gas vents must terminate with a listed cap or 
other roof assembly and be installed according to their 
manufacturer’s instructions.
Gas vents must be supported to prevent damage, joint 
separation, and maintain clearances to combustible 
materials (Figures 11 and 12).
IMPORTANT: This gas vent must be terminated in a 
vertical position to facilitate the removal of the burnt gases.
An unused chimney flue or masonry enclosure may be used 
as a passageway for the installation of a gas vent (Figure 12).
Common (combined) venting is allowable with vertical type 
B vent systems and lined masonry chimneys as long as 
proper draft for the water heater is established under all 
conditions of operation. CAUTION: DO NOT common vent 
this water heater with any power vented appliance.
Figures 10-12 are examples of vent pipe system 
installations and may or may not be typical for your 
specific application. Consult the “National Fuel Gas Code”, 
NFPA 54, ANSI Z223.1-current edition and the guidelines 
set forth by prevailing local codes.