Kenmore 153 User Manual

Page of 32
0
1.  Look at the top cover of the water heater. The hot water 
outlet is marked hot. Put two or three turns of teflon tape 
around the threaded end of the threaded-to-sweat coupling 
and around both ends of the 3/4” threaded nipple. Using 
flexible connectors, connect the hot water pipe to the hot 
water outlet of the water heater.
2.  Look at the top cover of the water heater. The cold water inlet 
is marked cold. Put two or three turns of teflon tape around 
the  threaded  end  of  the  threaded-to-sweat  coupling  and 
around both ends of the 3/4” threaded nipple. Using flexible 
connectors, connect the cold water pipe to the cold water inlet 
of the water heater.
NOTE:  Your  water  heater  is  insulated  to  minimize  heat 
loss from the tank. Further reduction in heat loss can be 
accomplished  by  insulating  the  hot  water  lines  from  the  
water heater.
FIGURE 8.
T & P Valve and Pipe Insulation
Remove insulation for T & P valve and pipe connections from 
carton.
Fit pipe insulation over the incoming cold water line and the hot 
water line. Make sure that the insulation is against the top cover 
of the heater.
Fit T & P valve insulation over valve. Make sure that the insulation 
does not interfere with the lever of the T & P valve.
Secure all insulation using tape.
FIGURE 9.
Temperature-Pressure Relief Valve
This  heater  is  provided  with  a  properly  certified  combination  
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory 
that  maintains  periodic  inspection  of  production  of  listed 
equipment of materials as meeting the requirements for Relief 
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, 
and the code requirements of ASME.
If replaced, the valve must meet the requirements of local codes, 
but not less than a combination temperature and pressure relief 
valve certified as indicated in the above paragraph.
The valve must be marked with a maximum set pressure not to 
exceed the marked hydrostatic working pressure of the water 
heater (150 psi = 1,035 kPa) and a discharge capacity not less 
than the water heater input rate as shown on the model rating plate. 
(For electric heaters, watts x 3.412 equals btu/hr input rate).
For safe operation of the water heater, the relief valve must not 
be removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly 
into the fitting of the water heater designed for the relief valve.  
Position  the  valve  downward  and  provide  tubing  so  that  any 
discharge will exit only within 6 inches (153 mm) above, or at any 
distance below the structural floor.  be certain that no contact is 
made with any live electrical part.  The discharge opening must 
not  be  blocked  or  reduced  in  size  under  any  circumstances.  
Excessive length, over 30 feet (9.14 m), or use of more than 
four  elbows  can  cause  restriction  and  reduce  the  discharge 
capacity of the valve.