OPERATION
IMPORTANT
A qualified person must perform the initial firing of the heater.  At 
this time the user should not hesitate to ask the individual any 
questions which they may have in regard to the operation and 
maintenance of the unit.
An Operational Checklist is included at the rear of this manual.  By 
using this checklist the user may be able to make minor operational 
adjustments and avoid unnecessary service calls.  However, the 
user should not attempt repairs which are not listed under the 
USER column.
GENERAL
NEVER  OPERATE  THE  HEATER  WITHOUT  FIRST  BEING 
CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE 
AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF 
VALVE OPENING OF THE HEATER.
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL 
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE 
TO THE APPLIANCE.
 
CAUTION
Before proceeding with the operation of the unit make sure 
the water heater and system are filled with water and all air
is expelled.
FILLING
1.  Close the heater drain valve by turning handle clockwise.
2.  Open a nearby hot water faucet to permit the air in the system 
to escape.
3.  Fully open the cold water inlet pipe valve  allowing the heater 
and piping to be filled.
4.  Close the hot water faucet as water starts to flow.
5.  The heater is ready to be operated.
 WARNING
THE GAS VALVE MUST HAVE BEEN IN THE OFF POSITION 
FOR AT LEAST 5 MINUTES. This waiting period is an important 
safety step. Its purpose is to permit gas that may have 
accumulated in the combustion chamber to clear. IF YOU 
DETECT GAS ODOR AT THE END OF THIS PERIOD DO NOT 
PROCEED WITH LIGHTING.  RECOGNIZE THAT GAS EVEN IF IT 
SEEMS WEAK, MAY INDICATE PRESENCE OF ACCUMULATED 
GAS SOMEPLACE IN THE AREA WITH RISK OF FIRE OR 
EXPLOSION.  SEE THE FRONT PAGE FOR STEPS TO BE TAKEN.
All gas and water lines leak tested and open.
Read 
SEQUENCE OF OPERATION
 
section of this manual prior 
to lighting and operating this appliance.
With above conditions satisfied, start the unit in accordance with 
the instructions on the Operating label attached to the heater.  If 
label instructions are not legible - determine which gas valve the 
appliance is equipped with and use the applicable 
OPERATING 
INSTRUCTIONS as follows:
Each  heater  is  equipped  with  an  ignition  control  board.   The 
controller will try three times to light the main burner before going 
into lockout.  After the controller tries three times, it will wait one 
hour before trying to light the unit again.  This cycle will continue 
until the main burners are ignited or the unit is shut down.
ADJUSTMENTS
ON INITIAL STARTUP SOME ADJUSTMENTS ARE NECESSARY.
1.  CHECK MANIFOLD AND INLET GAS PRESSURES.
2.  CYCLE CHECK - CHECK AT LEAST ONE BURNER 
OPERATION - WHEN THERMOSTAT IS SATISFIED, 
BURNER WILL SHUT OFF AND INDUCER WILL STOP 
RUNNING.  ON CALL FOR HEAT - THE INDUCER WILL 
COME ON AND CLOSE THE PRESSURE SWITCH AND 
THE IGNITION SEQUENCE DESCRIBED ABOVE WILL 
BEGIN, SEE “SEQUENCE OF OPERATION”.
SEQUENCE OF OPERATION
The following information will describe the Sequence of Operation 
for this appliance.
1.  Switch power on to unit.
2.  Thermostat calls for heat.
3.  Ignition Control Board performs diagnostic check on system 
components.
4.  On completion of diagnostics check, the Ignition Control Board 
sends signal to Exhaust Inducer.
5.  Exhaust Inducer begins drawing air through appliance closing 
the Prover Switch.
6.  On  completion  of  Prover  Switch  engagement,  the  Ignition 
Control Board begins the ignition cycle.
7.  The  Ignition  Control  Board  provides  power  to  the  Silicon 
Nitride Ignitor.
8.  The Silicon Nitride Ignitor heats up for approximately 17 to  
20 seconds.
9.  At the end of Silicon Nitride Ignitor’s warm-up, the Ignition 
Control Board opens the Gas Valve.
10.  From the time the Gas Valve opens, the Ignition Control Board 
waits 3 seconds and then shuts off power to the Silicon Nitride 
Ignitor.
11.  From the time the Silicon Nitride Ignitor’s power is shut off, 
the Ignition Control Board waits 3 more seconds to monitor 
the Flame Sensor.
12.  If the Flame Sensor does not detect a strong enough flame, 
the Ignition Control Board shuts off the Gas Valve and allows 
the Exhaust Inducer to purge the unit for 20 seconds.  At that 
time, the Ignition Control Board restarts with step 7.  It will try 
and ignite the main burners 2 more times.  If the unit does not 
light, the Ignition Control Board will wait one hour and then 
restart at step 3.  This cycle will continue until the unit lights 
or the power is shutoff to the unit.
13.  If the Flame Sensor detects a strong flame, the Ignition Control 
Board will allow the unit to operate until the thermostat is 
satisfied.
14.  Once the unit is satisfied, the Ignition Control Board will shut 
off the Gas Valve and the unit will be in standby mode until 
another call for heat is initiated by the thermostat.
See the flow chart on page 25 for more information.