Honeywell R7849 User Manual

Page of 8
R7824, R7847, R7848, R7849,R7851,R7861, R7886 AMPLIFIERS FOR 7800 SERIES RELAY MODULES
65-0109—8
4
CAUTION
Equipment Damage Hazard.
Incorrect combination of relay module, amplifier 
and flame detector can cause equipment damage.
In infrared applications (C7015 Infrared Flame 
Detector and R7848 Amplifier) using the RM7890 
Relay Module with software version 4004 or less 
requires a ten-second delay to start sequence. This 
applies only to the initial power of the RM7890.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous 
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced, flame 
safeguard control technician.
4. After installation is complete, check out the product 
operation as provided in these instructions.
WARNING
Electric Shock Hazard.
Can cause electrical shock, serious injury or 
death.
Disconnect the power supply before beginning 
installation. More than one power supply 
disconnection can be involved.
IMPORTANT
1. Wiring must comply with all applicable codes, 
ordinances and regulations
2. Wiring (where required) must comply with NEC 
Class 1 (Line Voltage) wiring.
3. Perform all required checkout tests after installation 
is complete. 
CAUTION
Equipment Damage Hazard.
Can cause equipment damage.
Disconnect 7800 SERIES Relay Module power before 
removing amplifier.
Installing Plug-In Flame 
Signal Amplifier (Fig. 2)
WARNING
Electric Shock Hazard.
Can cause electrical shock, serious injury or 
death.
Disconnect the power supply before beginning 
installation. More than one power supply 
disconnection can be involved.
1. Align the amplifier circuit board edge connector with the 
keyed receptacle on the 7800 SERIES Relay Module. 
Be sure the amplifier nameplate faces away from the 
Relay Module. 
2. Push in the amplifier until the circuit board is fully 
inserted into the receptacle and then push the amplifier 
toward the 7800 SERIES Relay Module retaining clasp. 
3. Be sure the amplifier is firmly in place.
4. Perform all required checkout tests. 
Installing Flame Detector
NOTE: NOTE:Table 2 lists flame detection systems available 
for use with 7800 SERIES Relay Modules. Be sure to 
use the correct combination of amplifier and flame 
detector.
Proper flame detector installation is the basis of a safe and 
reliable flame safeguard installation. Refer to the Instructions 
packed with the flame detector and the equipment manufac-
turer instructions. 
Keep the flame signal leadwires as short as possible from the 
flame detector to the wiring subbase. Capacitance increases 
with leadwire length, reducing the signal strength. The 
maximum permissible leadwire length depends on the type of 
flame detector, leadwire and conduit. However, the ultimate 
limiting factor for the flame detector leadwire is the flame 
signal; see Table 3 in the Checkout section.
Fig. 2.  Installing flame signal amplifier.
Wiring
WARNING
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before beginning installation. 
More than one disconnection can be involved. 
1. Remove the 7800 SERIES Relay Module from the 
wiring subbase. 
2. Refer to Fig. 3 for proper flame detector wiring.