Honeywell TB7220 User Manual

Page of 24
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
63-2635—03
6
Fig. 11. Restrict wires to shaded area of wire hole.
Table 4. Wiring Diagrams.
Table 5. Terminal Designation Descriptions.
NOTES:
1.
When used in a single-transformer system, leave 
metal jumper wire in place between Rc and R. If 
used on a two-transformer system, remove metal 
jumper wire between Rc and R.
2.
Common wire is optional when thermostat is used 
with batteries. When using separate transformers 
for heating and cooling, the common must come 
from the cooling transformer.
3.
If thermostat is configured for a heat pump in the 
Installer Setup, configure changeover valve for 
cool (O-factory setting) or heat (B).
4.
Reference economizer literature for wiring details. 
When set for economizer operation, the A terminal 
provides the occupancy signal. (Power indicates 
occupied.)
5.
Sensor wires must have a cable separate from the 
thermostat control cable.
Terminal “A” Wiring Details for Economizers
— Wire the A terminal to the W7212 “N” terminal, or the 
W7459 “TR” terminal.
— When using dual transformers at the thermostat, the cooling 
transformer must power the economizer.
— The A signal is powered from the R terminal and energizes 
the economizer to signal occupied status and drive the 
damper to the set minimum position.
System Type
Wallplate Terminal 
Identifications
Wiring Diagram 
Figure
Standard Heat/Cool Conventional
Heat Only
Conventional
Cool only
Conventional
Standard Multistage 
up to 2 Heat/2 Cool
Conventional
Heat Pump 
(No Auxiliary Heat)
Heat Pump
Heat Pump 
(with Auxiliary Heat)
Heat Pump
Multiple T7770A 
Sensors
Multiple C7189U 
Sensors
WALLPLATE
M22266
WALL OPENING
WIRE
SHADED AREA
Terminal 
Designation
Description
Rc 
(see Note 1)
Power for cooling—connect to secondary side 
of cooling system transformer.
(see Note 1)
Power for heating—connect to secondary side 
of heating system transformer.
Y
Compressor output.
(see Note 2)
Common wire from secondary side of cooling 
system transformer.
W
Heat relay.
G
Fan  relay.
W2
Second stage heat relay.
Y2
Second stage cooling.
O/B 
(see Note 3)
Changeover valve for heat pumps.
(see Note 4)
Economizer/Time-Of-Day (TOD) output—
powered via R terminal.
S1 
(See Note 5)
Optional outdoor or indoor remote sensor.
S2 
(See Note 5)
Optional outdoor or indoor remote sensor.