Activity Sensing does 
not exit when button 
pressed
All buttons are locked.
Make sure keypad lockout is disabled. Set IS code 18, value = 0.
Freeze Protection 
does not activate
System Type is set to 
Cool.
Freeze protection is not activated when system type is Cool (IS 
code 2; value = 1). Change System Type.
System mode is not Off.
Set the System mode button to Off.
Auto Fan Reset does 
not activate
Incorrect IS code.
Set the Installer Setup code #24 to Enabled (value = 1 or 2).
Calling for Heat/Cool 
setpoint couldn't be 
satisfied.
Only after the setpoint is satisfied, will the auto fan reset timer 
activate.
Table 8. Troubleshooting. (Continued)
Symptom Possible 
Cause 
Action